-
Notifications
You must be signed in to change notification settings - Fork 23
Serial Commands
Alan Weinstock edited this page Mar 14, 2019
·
3 revisions
To set the auto-tuning parameters using serial input, use the following:
- To change trigger active duration: TRG_D [integer for milliseconds]
- To change gain factor: GAIN_F [integer for gain state - see note*]
- To change sensor input pullup vRef high threshold: VADJH [float value]
- To change sensor input pullup vRef low threshold: VADJL [float value]
- To change comparator trigger high threshold: VCOMPH [float value]
- To change comparator trigger high threshold: VCOMPL [float value]
These commands should be wrapped in this format:
<CMD, INT, FLOAT>
You must include the unused variable for each instance.
Examples:
<GAIN_F, 3, 0.00>
<VADJH, 0, 2.35>
*Note for Gain Factor:
The gain STATE is representative of these values:
- 0 = 3x
- 1 = 3.5x
- 2 = 4.33x
- 3 = 6x
- 4 = 11x