Notes on Working With the ActuatorAgent

  • An agent can watch the window value from device state updates to perform scheduled actions within a timeslot.
    • If an Agent's Task is LOW_PREEMPT priority it can watch for device state updates where the window is less than or equal to the grace period (default 60.0).
  • When considering if to schedule long or multiple short time slots on a single device:
    • Do we need to ensure the device state for the duration between slots?
    • Yes. Schedule one long time slot instead.
    • No. Is it all part of the same Task or can we break it up in case there is a conflict with one of our time slots?
  • When considering time slots on multiple devices for a single Task:
    • Is the Task really dependent on all devices or is it actually multiple Tasks?
  • When considering priority:
    • Does the Task have to happen on an exact day?
    • No. Consider LOW and reschedule if preempted.
    • Yes. Use HIGH.
    • Is it problematic to prematurely stop a Task once started?
    • No. Consider LOW_PREEMPT and watch the device state updates for a small window value.
    • Yes. Consider LOW or HIGH.
  • If an agent is only observing but needs to assure that no another Task is going on while taking readings it can schedule the time to prevent other agents from messing with a devices state. The schedule updates can be used as a reminder as to when to start watching.
  • Any device, existing or not, can be scheduled. This allows for agents to schedule fake devices to create reminders to start working later rather then setting up their own internal timers and schedules.

Wiki Home

Quick Start Guide

Getting VOLTTRON

VOLTTRON Community

VOLTTRON Core Services

Historians

Drivers

Instance Management

Applications
  • ...
Examples
Developers
HOWTOS

VOLTTRON Versions and Features

Transactional Network Platform Overview

Platform Services

Volttron Restricted

Information Exchange Standards

FAQ

Project Home

Clone this wiki locally