Manual test - Test results not inputted into module_config
pass
connection.network.mac_address
Connection
Required Pass
Device MAC address is 9a:02:57:1e:8f:01
fail
connection.network.mac_oui
Connection
Required Pass
Manufacturer prefix not found!
skip
connection.switch.port_duplex
Connection
Required Pass
No local IP has been set, check system config
skip
connection.switch.port_link
Connection
Required Pass
No local IP has been set, check system config
skip
connection.switch.port_speed
Connection
Required Pass
No local IP has been set, check system config
skip
dns.network.hostname_resolution
DNS
Required Pass
Device did not send any DNS requests
pass
dot1x.dot1x
Other
Other
Authentication for 9a:02:57:1e:8f:01 succeeded.
pass
ntp.network.ntp_support
NTP
Required Pass
Using NTPv4.
pass
ntp.network.ntp_update
NTP
Required Pass
Device clock synchronized.
skip
poe.switch.power
PoE
Required Pass for PoE Devices
No local IP has been set, check system config
fail
protocol.bacext.pic
Protocol
Required Pass for BACnet Devices
PICS file defined however a BACnet device was not found.
skip
protocol.bacext.version
Protocol
Required Pass for BACnet Devices
Bacnet device not found.
skip
security.discover.firmware
Security
Required Pass for BACnet Devices
Could not retrieve a firmware version with nmap. Check bacnet port.
pass
security.nmap.http
Security
Required Pass
No running http servers have been found.
pass
security.nmap.ports
Security
Required Pass
Only allowed ports found open.
skip
security.password.http
Security
Required Pass
Port 80 not open on target device.
skip
security.password.https
Security
Required Pass
Port 443 not open on target device.
skip
security.password.ssh
Security
Required Pass
Port 22 not open on target device.
skip
security.password.telnet
Security
Required Pass
Port 23 not open on target device.
gone
security.ssh.version
Security
Required Pass
skip
security.tls.v1_2_client
Security
Required Pass
No client initiated TLS communication detected
skip
security.tls.v1_2_server
Security
Required Pass
IOException unable to connect to server.
skip
security.tls.v1_3_client
Security
Recommended Pass
No client initiated TLS communication detected
skip
security.tls.v1_3_server
Security
Recommended Pass
IOException unable to connect to server.
skip
security.tls.v1_server
Security
Required Pass
IOException unable to connect to server.
gone
unknown.fake.llama
Other
Other
gone
unknown.fake.monkey
Other
Other
Module pass
Module Config
Attribute
Value
enabled
True
Module fail
Module Config
Attribute
Value
enabled
True
Module ping
Report
--------------------
Baseline ping test report
LOCAL_IP not configured, assuming no network switch
Done with basic connectivity tests
--------------------
base.startup.dhcp
--------------------
Check the base DHCP startup exchange
--------------------
See log above
--------------------
RESULT pass base.startup.dhcp
--------------------
base.switch.ping
--------------------
Attempt to ping access switch (if configured)
--------------------
See log above
--------------------
RESULT skip base.switch.ping No local IP has been set, check system config
--------------------
connection.base.target_ping
--------------------
Attempt to ping the Device Under Test
--------------------
See log above
--------------------
RESULT pass connection.base.target_ping target reached
Module Config
Attribute
Value
enabled
True
Module nmap
Report
--------------------
security.nmap.ports
--------------------
Automatic TCP/UDP port scan using nmap
--------------------
# Nmap XXX scan initiated XXX as: nmap -v -n -T5 -sT -sU --host-timeout=4m --open -pU:47808,T:23,443,80, -oG XXX/tmp/nmap.log X.X.X.X
# Ports scanned: TCP(3;23,80,443) UDP(1;47808) SCTP(0;) PROTOCOLS(0;)
Host: X.X.X.X () Status: Up
Host: X.X.X.X () Ports: 47808/closed/udp//bacnet///
# Nmap done at XXX -- 1 IP address (1 host up) scanned in XXX
No invalid ports found.
--------------------
RESULT pass security.nmap.ports Only allowed ports found open.
--------------------
security.nmap.http
--------------------
Check that the device does not have open ports exposing an unencrypted web interface using HTTP
--------------------
# Nmap XXX scan initiated XXX as: nmap -v -n -T5 -A --script http-methods --host-timeout=4m --open -p- -oG XXX/tmp/http.log X.X.X.X
# Ports scanned: TCP(65535;1-65535) UDP(0;) SCTP(0;) PROTOCOLS(0;)
Host: X.X.X.X () Status: Up
Host: X.X.X.X () Ports: 10000/open/tcp//snet-sensor-mgmt?///
# Nmap done at XXX -- 1 IP address (1 host up) scanned in XXX
No running http servers have been found.
--------------------
RESULT pass security.nmap.http No running http servers have been found.
Module Config
Attribute
Value
timeout_sec
600
enabled
True
Module discover
Report
--------------------
security.discover.firmware
--------------------
Automatic bacnet firmware scan using nmap
--------------------
PORT STATE SERVICE
47808/udp closed bacnet
MAC Address: 9A:02:57:1E:8F:01 (Unknown)
--------------------
RESULT skip security.discover.firmware Could not retrieve a firmware version with nmap. Check bacnet port.
Module Config
Attribute
Value
enabled
True
Module switch
Report
--------------------
connection.switch.port_link
--------------------
Connect the device to the network switch. Check the device and the switch for the green connection light & no errors
--------------------
LOCAL_IP not configured, assuming no network switch.
--------------------
RESULT skip connection.switch.port_link No local IP has been set, check system config
--------------------
connection.switch.port_speed
--------------------
Verify the device auto-negotiates connection speed
--------------------
LOCAL_IP not configured, assuming no network switch.
--------------------
RESULT skip connection.switch.port_speed No local IP has been set, check system config
--------------------
connection.switch.port_duplex
--------------------
Verify the device supports full duplex
--------------------
LOCAL_IP not configured, assuming no network switch.
--------------------
RESULT skip connection.switch.port_duplex No local IP has been set, check system config
--------------------
poe.switch.power
--------------------
Verify that the device draws less than the maximum power allocated by the port. This is 15.4W for 802.3af and 30W for 802.3at
--------------------
LOCAL_IP not configured, assuming no network switch.
--------------------
RESULT skip poe.switch.power No local IP has been set, check system config
Module Config
Attribute
Value
enabled
True
timeout_sec
0
poe
{'enabled': True}
Module bacext
Report
--------------------
protocol.bacext.version
--------------------
Verify and record version of Bacnet used by the device
--------------------
Bacnet device not found.
--------------------
RESULT skip protocol.bacext.version Bacnet device not found.
--------------------
protocol.bacext.pic
--------------------
Verify BACnet traffic is compliant to the PIC statement
--------------------
PICS file defined however a BACnet device was not found.
--------------------
RESULT fail protocol.bacext.pic PICS file defined however a BACnet device was not found.
Module Config
Attribute
Value
enabled
True
Module tls
Report
--------------------
Collecting TLS cert from target address
Gathering TLS 1 Server Information....
TLS 1Server Implementation Skipping Test, could not open connection
TLS 1 Server Information Complete.
Gathering TLS 1.2 Server Information....
TLS 1.2Server Implementation Skipping Test, could not open connection
TLS 1.2 Server Information Complete.
Gathering TLS 1.3 Server Information....
TLS 1.3Server Implementation Skipping Test, could not open connection
TLS 1.3 Server Information Complete.
Gathering TLS Client X.X.X.X Information....
TLS Client Information Complete.
Gathering TLS Client X.X.X.X Information....
TLS Client Information Complete.
--------------------
security.tls.v1_2_client
--------------------
Verify the device supports at least TLS 1.2 (as a client)
--------------------
See log above
--------------------
RESULT skip security.tls.v1_2_client No client initiated TLS communication detected
--------------------
security.tls.v1_2_server
--------------------
Verify the device supports TLS 1.2 (as a server)
--------------------
See log above
--------------------
RESULT skip security.tls.v1_2_server IOException unable to connect to server.
--------------------
security.tls.v1_3_client
--------------------
Verify the device supports at least TLS 1.3 (as a client)
--------------------
See log above
--------------------
RESULT skip security.tls.v1_3_client No client initiated TLS communication detected
--------------------
security.tls.v1_3_server
--------------------
Verify the device supports TLS 1.3 (as a server)
--------------------
See log above
--------------------
RESULT skip security.tls.v1_3_server IOException unable to connect to server.
--------------------
security.tls.v1_server
--------------------
Verify the device supports at least TLS 1.0 (as a server)
--------------------
See log above
--------------------
RESULT skip security.tls.v1_server IOException unable to connect to server.
Module Config
Attribute
Value
enabled
True
timeout_sec
0
ca_file
CA_Faux.pem
Module password
Report
--------------------
security.admin.password.http
--------------------
Verify all device manufacturer default passwords are changed for protocol: http, and new passwords are set.
--------------------
Starting Nmap 7.60 ( https://nmap.org ) at XXX
Nmap scan report for daq-faux-1 (X.X.X.X)
Host is up (XXX).
PORT STATE SERVICE
80/tcp closed http
MAC Address: 9A:02:57:1E:8F:01 (Unknown)
Nmap done: 1 IP address (1 host up) scanned in XXX
Could not connect to specified port on host.
--------------------
RESULT skip security.password.http Port 80 not open on target device.
--------------------
security.admin.password.https
--------------------
Verify all device manufacturer default passwords are changed for protocol: https, and new passwords are set.
--------------------
Starting Nmap 7.60 ( https://nmap.org ) at XXX
Nmap scan report for daq-faux-1 (X.X.X.X)
Host is up (XXX).
PORT STATE SERVICE
443/tcp closed https
MAC Address: 9A:02:57:1E:8F:01 (Unknown)
Nmap done: 1 IP address (1 host up) scanned in XXX
Could not connect to specified port on host.
--------------------
RESULT skip security.password.https Port 443 not open on target device.
--------------------
security.admin.password.ssh
--------------------
Verify all device manufacturer default passwords are changed for protocol: ssh, and new passwords are set.
--------------------
Starting Nmap 7.60 ( https://nmap.org ) at XXX
Nmap scan report for daq-faux-1 (X.X.X.X)
Host is up (XXX).
PORT STATE SERVICE
22/tcp closed ssh
MAC Address: 9A:02:57:1E:8F:01 (Unknown)
Nmap done: 1 IP address (1 host up) scanned in XXX
Could not connect to specified port on host.
--------------------
RESULT skip security.password.ssh Port 22 not open on target device.
--------------------
security.admin.password.telnet
--------------------
Verify all device manufacturer default passwords are changed for protocol: telnet, and new passwords are set.
--------------------
Starting Nmap 7.60 ( https://nmap.org ) at XXX
Nmap scan report for daq-faux-1 (X.X.X.X)
Host is up (XXX).
PORT STATE SERVICE
23/tcp closed telnet
MAC Address: 9A:02:57:1E:8F:01 (Unknown)
Nmap done: 1 IP address (1 host up) scanned in XXX
Could not connect to specified port on host.
--------------------
RESULT skip security.password.telnet Port 23 not open on target device.
Module Config
Attribute
Value
enabled
True
timeout_sec
0
dictionary_dir
resources/faux
Module udmi
Report
--------------------
cloud.udmi.provision
--------------------
Validates device provision payload.
--------------------
No device id
--------------------
RESULT skip cloud.udmi.provision No device id
--------------------
cloud.udmi.state_system
--------------------
Validates device state_system payload.
--------------------
No device id
--------------------
RESULT skip cloud.udmi.state_system No device id
--------------------
cloud.udmi.state_pointset
--------------------
Validates device state_pointset payload.
--------------------
No device id
--------------------
RESULT skip cloud.udmi.state_pointset No device id
--------------------
cloud.udmi.event_system
--------------------
Validates device event_system payload.
--------------------
No device id
--------------------
RESULT skip cloud.udmi.event_system No device id
--------------------
cloud.udmi.event_pointset
--------------------
Validates device event_pointset payload.
--------------------
No device id
--------------------
RESULT skip cloud.udmi.event_pointset No device id
Module Config
Attribute
Value
enabled
True
Module manual
Report
--------------------
connection.manual.comms_down
--------------------
--------------------
No additional information provided
--------------------
RESULT pass connection.manual.comms_down Manual test - Device passed this manual test
--------------------
connection.manual.sec_eth_port
--------------------
--------------------
No additional information provided
--------------------
RESULT skip connection.manual.sec_eth_port Manual test - Test results not inputted into module_config
Module Config
Attribute
Value
enabled
True
Module network
Report
--------------------
communication.network.min_send
--------------------
Device sends data at a frequency of less than 5 minutes.
--------------------
RESULT pass communication.network.min_send ARP packets received. Data packets were sent at a frequency of less than 5 minutes
--------------------
communication.network.type
--------------------
Device sends unicast or broadcast packets.
--------------------
RESULT pass communication.network.type Broadcast packets received. Unicast packets received.
--------------------
ntp.network.ntp_support
--------------------
Device supports NTP version 4.
--------------------
RESULT pass ntp.network.ntp_support Using NTPv4.
--------------------
ntp.network.ntp_update
--------------------
Device synchronizes its time to the NTP server.
--------------------
RESULT pass ntp.network.ntp_update Device clock synchronized.
--------------------
connection.network.mac_oui
--------------------
Check Physical device address OUI against IEEE registration and verify it is registered with the correct manufacturer
--------------------
Using the host hardware address 9a:02:57:1e:8f:01
Mac OUI Test
--------------------
RESULT fail connection.network.mac_oui Manufacturer prefix not found!
--------------------
connection.network.mac_address
--------------------
Reports device MAC address
--------------------
Device MAC address is 9a:02:57:1e:8f:01
--------------------
RESULT pass connection.network.mac_address Device MAC address is 9a:02:57:1e:8f:01
--------------------
dns.network.hostname_resolution
--------------------
Check device uses the DNS server from DHCP and resolves hostnames
--------------------
RESULT skip dns.network.hostname_resolution Device did not send any DNS requests
Module Config
Attribute
Value
enabled
True
Module dot1x
Report
--------------------
dot1x.dot1x
--------------------
Dot1x authentication tests
--------------------
n/a
--------------------
RESULT pass dot1x.dot1x Authentication for 9a:02:57:1e:8f:01 succeeded.