Skip to content
Paul Norman edited this page Dec 18, 2023 · 84 revisions

AM6 rack contents

Rack # Equipment Network 1 Network 2 OOB Network Power 1 Power 2 Notes
47 Patch panel PP:1625:1131589 ge-0/2/2: 22519284-A PP: port 3 ge-1/2/2: 22519301-A PP: port 6 Old Cogent Link: 20812113 (decommission) PP: port 1
46 Cable organizer
45
44 Boxes on Shelf
43 Boxes on Shelf
42 Boxes on Shelf
41 Boxes on Shelf
40 Boxes on Shelf
39 Boxes on Shelf
38 Boxes on Shelf
37 Boxes on Shelf
36 Boxes on Shelf
35 Boxes on Shelf
34 Boxes on Shelf
33 Shelf
32 tabaluga (parts) ge0/0/1 ge1/0/1 ge-1/0/24 A1: 500W 720478-B21 B1: 500W 720478-B21
31
30
29
28
27
26
25
24
23 Juniper SW1 (front) 22519301-A PP port 6 ge-1/2/2 A12: 350W PSU B12: 350W PSU
22 Juniper SW2 (front) 22519284-A PP port 3 ge-0/2/2 A13: 350W PSU B13: 350W PSU
21
20
19 odin ge-0/0/2 ge-1/0/2 ge-0/0/30 A10: 700W PWS-706P-1R B10: 700W PWS-706P-1R
18 norbert ge-0/0/3 ge-1/0/3 ge-1/0/29 A11: 1200W PWS-1K22A-1R B11: 1200W PWS-1K22A-1R Power uses C19/20 to C13/14 cable
17 vhagar ge-0/0/9 ge-1/0/9 ge-0/0/34 A9: 500W 720478-B21 A9: 500W 720478-B21 Only 2 nvme bays.
16 dulcy ge-0/0/22 ge-1/0/22 ge-1/0/30 A17: 1000W PWS-1K02A-1R B17: 1000W PWS-1K02A-1R
15 snap-01 (2U) ge-0/0/16 ge-1/0/16 ge-0/0/28 A18: 1600W PWS-1K62A-1R B18: 1600W PWS-1K62A-1R
14 snap-01 (2U) - - - - -
13 spike-08 ge-0/0/21 ge-1/0/21 ge-0/0/27 A19: 500W 720478-B21 B19: 500W 720478-B21
12 spike-07 ge-0/0/18 ge-1/0/18 ge-1/0/27 A14: 500W 720478-B21 B14: 500W 720478-B21
11 spike-06 ge-0/0/20 ge-1/0/20 ge-0/0/31 A15: 500W 720478-B21 B15: 500W 720478-B21
10
9
8
7
6 dribble ge-0/0/15 ge-1/0/15 ge-0/0/33 A20: 500W 720478-B21 B20: 500W 720478-B21 Only 2 nvme bays.
5 faffy ge-0/0/23 ge-1/0/23 ge-0/0/29 A21: 800W 720479-B21 B21: 800W 720479-B21 2 free NVMe bays, trays required
4 karm (2U) ge-0/0/19 ge-1/0/19 ge-1/0/25 A22: 1000W PWS-1K02A-1R B22: 1000W PWS-1K02A-1R
3 karm (2U) - - - - -
2 ironbelly (2U) ge-0/0/17 ge-1/0/17 ge-1/0/26 A23: 920W PWS-920P-SQ B23: 920W PWS-920P-SQ
1 ironbelly (2U) - - - - -
0 (floor) oob1 (RPI4) ge-0/0/25 ge-1/0/34 - A24: 15W SC0216 (via UK plug adapter) B24: 15W SC0443 (via UK plug strip) Dual Power Adapter. 4G modem above rack
left PDU PDU-A / PDU1 - - ge-0/0/35 - -
right PDU PDU-B / PDU2 - - ge-1/0/32 - -

Notes

  • Black power cables for A side, white power cables for B side
  • Black ethernet cables for switch 1 (top), blue ethernet cables for switch 2 (bottom)
  • Beige ethernet cables for OOB
  • Blue fiber for uplink
  • Plugs 8 and 16 on both PDUs are higher current C19 sockets with C19/C19 adapter and are not connected. Ethernet 8 and 16 are left unused on the switches to keep numbering consistent.
  • Plug 24 on both PDUs use C19/C13 adapters which are connected to UK sockets. PDU-A is a single socket. PDU-B is a 4x UK socket strip.
  • The back of the rack is very tight between the PDUs. It is nearly impossible to take stuff out horizontally out the back of the rack.
Clone this wiki locally