Vehicle is not charging and there are no error messages. #34

Open
RealBlade85 opened this issue Nov 13, 2024 · 0 comments
Open

Vehicle is not charging and there are no error messages. #34

RealBlade85 opened this issue Nov 13, 2024 · 0 comments

Comments

@RealBlade85
Copy link

RealBlade85 commented Nov 13, 2024

Hello dear community.

I have a Huawei inverter and a BMW IX as a vehicle and a Webasto Unite Wallbox.
So far so well everything was configured, but unfortunately loading doesn't start.

Here is the Log. Does anyone have any advice?

[main ] INFO 2024/11/13 08:53:38 evcc 0.131.5
[main ] INFO 2024/11/13 08:53:38 using config file: /config/evcc.yaml
[db ] INFO 2024/11/13 08:53:38 using sqlite database: /data/evcc.db
[main ] INFO 2024/11/13 08:53:39 listening at :7070
[lp-1 ] DEBUG 2024/11/13 08:53:40 charge total import: 110.000kWh
[site ] INFO 2024/11/13 08:53:40 site config:
[site ] INFO 2024/11/13 08:53:40 meters: grid ✓ pv ✓ battery ✗
[site ] INFO 2024/11/13 08:53:40 grid: power ✓ energy ✓ currents ✓
[site ] INFO 2024/11/13 08:53:40 pv 1: power ✓ energy ✓ currents ✗
[site ] INFO 2024/11/13 08:53:40 vehicles:
[site ] INFO 2024/11/13 08:53:40 vehicle 1: range ✓ finish ✗ status ✓ climate ✗ wakeup ✓
[lp-1 ] INFO 2024/11/13 08:53:40 loadpoint 1:
[lp-1 ] INFO 2024/11/13 08:53:40 mode: off
[lp-1 ] INFO 2024/11/13 08:53:40 charger: power ✓ energy ✓ currents ✓ phases ✗ wakeup ✗
[lp-1 ] INFO 2024/11/13 08:53:40 meters: charge ✓
[lp-1 ] INFO 2024/11/13 08:53:40 charge: power ✓ energy ✓ currents ✓
[lp-1 ] DEBUG 2024/11/13 08:53:40 phase timer inactive
[lp-1 ] DEBUG 2024/11/13 08:53:40 pv timer inactive
[site ] DEBUG 2024/11/13 08:53:40 ----
[lp-1 ] DEBUG 2024/11/13 08:53:40 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:53:40 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:53:41 modbus: send 00 01 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:53:43 modbus: recv 00 01 00 00 00 07 01 03 04 ff ff fa 30
[site ] DEBUG 2024/11/13 08:53:43 grid power: 1488W
[db:1 ] TRACE 2024/11/13 08:53:43 modbus: send 00 02 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:53:44 modbus: recv 00 02 00 00 00 07 01 03 04 ff ff fe 0e
[my_pv ] TRACE 2024/11/13 08:53:44 modbus: send 00 03 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:53:44 modbus: recv 00 03 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:53:44 modbus: send 00 04 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:53:45 modbus: recv 00 04 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:53:45 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:53:45 modbus: send 00 05 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:53:46 modbus: recv 00 05 00 00 00 07 01 03 04 ff ff ff 6a
[db:1 ] TRACE 2024/11/13 08:53:46 modbus: send 00 06 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:53:47 modbus: recv 00 06 00 00 00 07 01 03 04 ff ff ff 93
[site ] DEBUG 2024/11/13 08:53:47 grid currents: [4.98 1.5 1.09]A
[db:1 ] TRACE 2024/11/13 08:53:47 modbus: send 00 07 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:53:47 modbus: recv 00 07 00 00 00 07 01 03 04 00 02 22 c2
[site ] DEBUG 2024/11/13 08:53:47 site power: 1488W
[lp-1 ] DEBUG 2024/11/13 08:53:47 charge voltages: [237 239 239]V
[lp-1 ] DEBUG 2024/11/13 08:53:47 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:53:47 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:53:47 charger status: B
[lp-1 ] INFO 2024/11/13 08:53:47 car connected
[lp-1 ] DEBUG 2024/11/13 08:53:47 vehicle api refresh
[lp-1 ] DEBUG 2024/11/13 08:53:47 pv timer elapse
[lp-1 ] DEBUG 2024/11/13 08:53:47 pv timer inactive
[lp-1 ] DEBUG 2024/11/13 08:53:47 charge total import: 110.000kWh
[main ] DEBUG 2024/11/13 08:53:48 vehicle status: B (IX)
[lp-1 ] INFO 2024/11/13 08:53:48 vehicle updated: unknown -> IX
[lp-1 ] DEBUG 2024/11/13 08:53:48 vehicle status: B
[lp-1 ] DEBUG 2024/11/13 08:53:48 vehicle soc: 32%
[lp-1 ] DEBUG 2024/11/13 08:53:48 vehicle soc limit: 100%
[lp-1 ] DEBUG 2024/11/13 08:53:48 vehicle range: 99km
[site ] DEBUG 2024/11/13 08:54:10 ----
[lp-1 ] DEBUG 2024/11/13 08:54:10 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:54:10 charge currents: [0 0 0]A
[my_pv ] TRACE 2024/11/13 08:54:10 modbus: send 00 08 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:54:10 modbus: close connection and retry, because of EOF
[my_pv ] TRACE 2024/11/13 08:54:26 modbus: send 00 08 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:54:27 modbus: recv 00 08 00 00 00 07 01 03 04 00 00 00 00
[db:1 ] TRACE 2024/11/13 08:54:27 modbus: send 00 09 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:54:27 modbus: recv 00 09 00 00 00 07 01 03 04 ff ff fa 37
[site ] DEBUG 2024/11/13 08:54:27 grid power: 1481W
[my_pv ] TRACE 2024/11/13 08:54:27 modbus: send 00 0a 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:54:27 modbus: recv 00 0a 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:54:27 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:54:27 modbus: send 00 0b 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:54:29 modbus: recv 00 0b 00 00 00 07 01 03 04 ff ff fe 12
[db:1 ] TRACE 2024/11/13 08:54:29 modbus: send 00 0c 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:54:29 modbus: recv 00 0c 00 00 00 07 01 03 04 ff ff ff 6a
[db:1 ] TRACE 2024/11/13 08:54:29 modbus: send 00 0d 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:54:29 modbus: recv 00 0d 00 00 00 07 01 03 04 ff ff ff 91
[site ] DEBUG 2024/11/13 08:54:29 grid currents: [4.94 1.5 1.11]A
[db:1 ] TRACE 2024/11/13 08:54:29 modbus: send 00 0e 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:54:30 modbus: recv 00 0e 00 00 00 07 01 03 04 00 02 22 c4
[site ] DEBUG 2024/11/13 08:54:30 site power: 1481W
[lp-1 ] DEBUG 2024/11/13 08:54:30 vehicle odometer: 41614km
[lp-1 ] DEBUG 2024/11/13 08:54:30 charge voltages: [237 239 240]V
[lp-1 ] DEBUG 2024/11/13 08:54:30 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:54:30 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:54:30 charger status: B
[site ] DEBUG 2024/11/13 08:54:40 ----
[lp-1 ] DEBUG 2024/11/13 08:54:40 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:54:40 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:54:40 modbus: send 00 0f 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:54:40 modbus: close connection and retry, because of EOF
[db:1 ] TRACE 2024/11/13 08:54:56 modbus: send 00 0f 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:54:56 modbus: recv 00 0f 00 00 00 07 01 03 04 ff ff fa 42
[site ] DEBUG 2024/11/13 08:54:56 grid power: 1470W
[db:1 ] TRACE 2024/11/13 08:54:56 modbus: send 00 10 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:54:57 modbus: recv 00 10 00 00 00 07 01 03 04 ff ff fe 14
[my_pv ] TRACE 2024/11/13 08:54:57 modbus: send 00 11 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:54:58 modbus: recv 00 11 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:54:58 modbus: send 00 12 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:54:58 modbus: recv 00 12 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:54:58 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:54:58 modbus: send 00 13 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:54:59 modbus: recv 00 13 00 00 00 07 01 03 04 ff ff ff 6a
[db:1 ] TRACE 2024/11/13 08:54:59 modbus: send 00 14 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:55:00 modbus: recv 00 14 00 00 00 07 01 03 04 ff ff ff 93
[site ] DEBUG 2024/11/13 08:55:00 grid currents: [4.92 1.5 1.09]A
[db:1 ] TRACE 2024/11/13 08:55:00 modbus: send 00 15 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:55:00 modbus: recv 00 15 00 00 00 07 01 03 04 00 02 22 c5
[site ] DEBUG 2024/11/13 08:55:00 site power: 1470W
[lp-1 ] DEBUG 2024/11/13 08:55:00 charge voltages: [238 239 240]V
[lp-1 ] DEBUG 2024/11/13 08:55:00 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:55:00 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:55:00 charger status: B
[site ] DEBUG 2024/11/13 08:55:10 ----
[lp-1 ] DEBUG 2024/11/13 08:55:10 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:55:10 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:55:10 modbus: send 00 16 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:55:11 modbus: recv 00 16 00 00 00 07 01 03 04 ff ff fa 37
[site ] DEBUG 2024/11/13 08:55:11 grid power: 1481W
[my_pv ] TRACE 2024/11/13 08:55:11 modbus: send 00 17 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:55:11 modbus: recv 00 17 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:55:11 modbus: send 00 18 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:55:11 modbus: recv 00 18 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:55:11 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:55:11 modbus: send 00 19 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:55:12 modbus: recv 00 19 00 00 00 07 01 03 04 ff ff fe 13
[db:1 ] TRACE 2024/11/13 08:55:12 modbus: send 00 1a 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:55:13 modbus: recv 00 1a 00 00 00 07 01 03 04 ff ff ff 6a
[db:1 ] TRACE 2024/11/13 08:55:13 modbus: send 00 1b 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:55:14 modbus: recv 00 1b 00 00 00 07 01 03 04 ff ff ff 91
[site ] DEBUG 2024/11/13 08:55:14 grid currents: [4.93 1.5 1.11]A
[db:1 ] TRACE 2024/11/13 08:55:14 modbus: send 00 1c 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:55:14 modbus: close connection and retry, because of EOF
[db:1 ] TRACE 2024/11/13 08:55:30 modbus: send 00 1c 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:55:31 modbus: recv 00 1c 00 00 00 07 01 03 04 00 02 22 c8
[site ] DEBUG 2024/11/13 08:55:31 site power: 1481W
[lp-1 ] DEBUG 2024/11/13 08:55:31 charge voltages: [239 240 241]V
[lp-1 ] DEBUG 2024/11/13 08:55:31 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:55:31 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:55:31 charger status: B
[site ] DEBUG 2024/11/13 08:55:40 ----
[lp-1 ] DEBUG 2024/11/13 08:55:40 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:55:40 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:55:40 modbus: send 00 1d 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:55:41 modbus: recv 00 1d 00 00 00 07 01 03 04 ff ff fa 3a
[site ] DEBUG 2024/11/13 08:55:41 grid power: 1478W
[db:1 ] TRACE 2024/11/13 08:55:41 modbus: send 00 1e 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:55:41 modbus: recv 00 1e 00 00 00 07 01 03 04 ff ff fe 12
[my_pv ] TRACE 2024/11/13 08:55:41 modbus: send 00 1f 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:55:41 modbus: recv 00 1f 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:55:41 modbus: send 00 20 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:55:42 modbus: recv 00 20 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:55:42 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:55:42 modbus: send 00 21 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:55:43 modbus: recv 00 21 00 00 00 07 01 03 04 ff ff ff 69
[db:1 ] TRACE 2024/11/13 08:55:43 modbus: send 00 22 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:55:43 modbus: recv 00 22 00 00 00 07 01 03 04 ff ff ff 94
[site ] DEBUG 2024/11/13 08:55:43 grid currents: [4.94 1.51 1.08]A
[db:1 ] TRACE 2024/11/13 08:55:43 modbus: send 00 23 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:55:44 modbus: recv 00 23 00 00 00 07 01 03 04 00 02 22 c8
[site ] DEBUG 2024/11/13 08:55:44 site power: 1478W
[lp-1 ] DEBUG 2024/11/13 08:55:44 charge voltages: [239 241 241]V
[lp-1 ] DEBUG 2024/11/13 08:55:44 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:55:44 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:55:44 charger status: B
[site ] DEBUG 2024/11/13 08:56:10 ----
[lp-1 ] DEBUG 2024/11/13 08:56:10 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:56:10 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:56:10 modbus: send 00 24 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:56:10 modbus: close connection and retry, because of EOF
[db:1 ] TRACE 2024/11/13 08:56:26 modbus: send 00 24 00 00 00 06 01 03 90 f9 00 02
[lp-1 ] DEBUG 2024/11/13 08:56:26 set charge mode: now
[lp-1 ] DEBUG 2024/11/13 08:56:26 pv timer reset
[lp-1 ] DEBUG 2024/11/13 08:56:26 pv timer inactive
[db:1 ] TRACE 2024/11/13 08:56:26 modbus: recv 00 24 00 00 00 07 01 03 04 ff ff fa 33
[site ] DEBUG 2024/11/13 08:56:26 grid power: 1485W
[db:1 ] TRACE 2024/11/13 08:56:26 modbus: send 00 25 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:56:27 modbus: recv 00 25 00 00 00 07 01 03 04 ff ff fe 0c
[my_pv ] TRACE 2024/11/13 08:56:27 modbus: send 00 26 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:56:27 modbus: recv 00 26 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:56:27 modbus: send 00 27 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:56:28 modbus: recv 00 27 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:56:28 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:56:28 modbus: send 00 28 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:56:29 modbus: recv 00 28 00 00 00 07 01 03 04 ff ff ff 6a
[db:1 ] TRACE 2024/11/13 08:56:29 modbus: send 00 29 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:56:29 modbus: recv 00 29 00 00 00 07 01 03 04 ff ff ff 95
[site ] DEBUG 2024/11/13 08:56:29 grid currents: [5 1.5 1.07]A
[db:1 ] TRACE 2024/11/13 08:56:29 modbus: send 00 2a 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:56:29 modbus: recv 00 2a 00 00 00 07 01 03 04 00 02 22 ca
[site ] DEBUG 2024/11/13 08:56:29 site power: 1485W
[lp-1 ] DEBUG 2024/11/13 08:56:29 charge voltages: [239 240 241]V
[lp-1 ] DEBUG 2024/11/13 08:56:29 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:56:29 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:56:29 charger status: B
[lp-1 ] DEBUG 2024/11/13 08:56:29 max charge current: 13A
[lp-1 ] DEBUG 2024/11/13 08:56:29 charger enable
[lp-1 ] DEBUG 2024/11/13 08:56:29 wake-up timer: start
[site ] DEBUG 2024/11/13 08:56:29 ----
[lp-1 ] DEBUG 2024/11/13 08:56:29 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:56:29 charge currents: [0 0 0]A
[my_pv ] TRACE 2024/11/13 08:56:29 modbus: send 00 2b 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:56:30 modbus: recv 00 2b 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:56:30 modbus: send 00 2c 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:56:31 modbus: recv 00 2c 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:56:31 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:56:31 modbus: send 00 2d 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:56:31 modbus: recv 00 2d 00 00 00 07 01 03 04 ff ff fa 2f
[site ] DEBUG 2024/11/13 08:56:31 grid power: 1489W
[db:1 ] TRACE 2024/11/13 08:56:31 modbus: send 00 2e 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:56:32 modbus: recv 00 2e 00 00 00 07 01 03 04 ff ff fe 0c
[db:1 ] TRACE 2024/11/13 08:56:32 modbus: send 00 2f 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:56:32 modbus: recv 00 2f 00 00 00 07 01 03 04 ff ff ff 68
[db:1 ] TRACE 2024/11/13 08:56:32 modbus: send 00 30 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:56:33 modbus: recv 00 30 00 00 00 07 01 03 04 ff ff ff 94
[site ] DEBUG 2024/11/13 08:56:33 grid currents: [5 1.52 1.08]A
[db:1 ] TRACE 2024/11/13 08:56:33 modbus: send 00 31 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:56:34 modbus: recv 00 31 00 00 00 07 01 03 04 00 02 22 ca
[site ] DEBUG 2024/11/13 08:56:34 site power: 1489W
[lp-1 ] DEBUG 2024/11/13 08:56:34 charge voltages: [239 240 241]V
[lp-1 ] DEBUG 2024/11/13 08:56:34 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:56:34 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:56:34 charger status: B
[site ] DEBUG 2024/11/13 08:56:40 ----
[lp-1 ] DEBUG 2024/11/13 08:56:40 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:56:40 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:56:40 modbus: send 00 32 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:56:41 modbus: recv 00 32 00 00 00 07 01 03 04 ff ff fa 3a
[site ] DEBUG 2024/11/13 08:56:41 grid power: 1478W
[db:1 ] TRACE 2024/11/13 08:56:41 modbus: send 00 33 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:56:41 modbus: recv 00 33 00 00 00 07 01 03 04 ff ff fe 0b
[my_pv ] TRACE 2024/11/13 08:56:41 modbus: send 00 34 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:56:41 modbus: recv 00 34 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:56:41 modbus: send 00 35 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:56:42 modbus: recv 00 35 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:56:42 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:56:42 modbus: send 00 36 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:56:43 modbus: recv 00 36 00 00 00 07 01 03 04 ff ff ff 6a
[db:1 ] TRACE 2024/11/13 08:56:43 modbus: send 00 37 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:56:43 modbus: recv 00 37 00 00 00 07 01 03 04 ff ff ff 97
[site ] DEBUG 2024/11/13 08:56:43 grid currents: [5.01 1.5 1.05]A
[db:1 ] TRACE 2024/11/13 08:56:43 modbus: send 00 38 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:56:44 modbus: recv 00 38 00 00 00 07 01 03 04 00 02 22 ca
[site ] DEBUG 2024/11/13 08:56:44 site power: 1478W
[lp-1 ] DEBUG 2024/11/13 08:56:44 charge voltages: [239 240 241]V
[lp-1 ] DEBUG 2024/11/13 08:56:44 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:56:44 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:56:44 charger status: B
[site ] DEBUG 2024/11/13 08:57:10 ----
[lp-1 ] DEBUG 2024/11/13 08:57:10 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:57:10 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:57:10 modbus: send 00 39 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:57:10 modbus: close connection and retry, because of EOF
[db:1 ] TRACE 2024/11/13 08:57:26 modbus: send 00 39 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:57:27 modbus: recv 00 39 00 00 00 07 01 03 04 ff ff fa 3c
[site ] DEBUG 2024/11/13 08:57:27 grid power: 1476W
[db:1 ] TRACE 2024/11/13 08:57:27 modbus: send 00 3a 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:57:27 modbus: recv 00 3a 00 00 00 07 01 03 04 ff ff fe 03
[my_pv ] TRACE 2024/11/13 08:57:27 modbus: send 00 3b 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:57:28 modbus: recv 00 3b 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:57:28 modbus: send 00 3c 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:57:29 modbus: recv 00 3c 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:57:29 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:57:29 modbus: send 00 3d 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:57:29 modbus: recv 00 3d 00 00 00 07 01 03 04 ff ff ff 6b
[db:1 ] TRACE 2024/11/13 08:57:29 modbus: send 00 3e 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:57:30 modbus: recv 00 3e 00 00 00 07 01 03 04 ff ff ff 9e
[site ] DEBUG 2024/11/13 08:57:30 grid currents: [5.09 1.49 0.98]A
[db:1 ] TRACE 2024/11/13 08:57:30 modbus: send 00 3f 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:57:30 modbus: recv 00 3f 00 00 00 07 01 03 04 00 02 22 cc
[site ] DEBUG 2024/11/13 08:57:30 site power: 1476W
[lp-1 ] DEBUG 2024/11/13 08:57:30 charge voltages: [239 241 241]V
[lp-1 ] DEBUG 2024/11/13 08:57:30 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:57:30 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:57:30 charger status: B
[site ] DEBUG 2024/11/13 08:57:40 ----
[lp-1 ] DEBUG 2024/11/13 08:57:40 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:57:40 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:57:40 modbus: send 00 40 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:57:40 modbus: close connection and retry, because of EOF
[db:1 ] TRACE 2024/11/13 08:57:56 modbus: send 00 40 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:57:58 modbus: recv 00 40 00 00 00 07 01 03 04 ff ff fa 39
[site ] DEBUG 2024/11/13 08:57:58 grid power: 1479W
[my_pv ] TRACE 2024/11/13 08:57:58 modbus: send 00 41 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:57:59 modbus: recv 00 41 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:57:59 modbus: send 00 42 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:58:01 modbus: recv 00 42 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:58:01 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:58:01 modbus: send 00 43 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:58:01 modbus: recv 00 43 00 00 00 07 01 03 04 ff ff fd fd
[db:1 ] TRACE 2024/11/13 08:58:01 modbus: send 00 44 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:58:02 modbus: recv 00 44 00 00 00 07 01 03 04 ff ff ff 6a
[db:1 ] TRACE 2024/11/13 08:58:02 modbus: send 00 45 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:58:02 modbus: recv 00 45 00 00 00 07 01 03 04 ff ff ff a0
[site ] DEBUG 2024/11/13 08:58:02 grid currents: [5.15 1.5 0.96]A
[db:1 ] TRACE 2024/11/13 08:58:02 modbus: send 00 46 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:58:03 modbus: recv 00 46 00 00 00 07 01 03 04 00 02 22 cd
[site ] DEBUG 2024/11/13 08:58:03 site power: 1479W
[lp-1 ] DEBUG 2024/11/13 08:58:03 charge voltages: [239 241 242]V
[lp-1 ] DEBUG 2024/11/13 08:58:03 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:58:03 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:58:03 charger status: B
[lp-1 ] DEBUG 2024/11/13 08:58:03 wake-up vehicle, attempts left: 4
[site ] DEBUG 2024/11/13 08:58:10 ----
[lp-1 ] DEBUG 2024/11/13 08:58:10 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:58:10 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:58:10 modbus: send 00 47 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:58:10 modbus: close connection and retry, because of EOF
[db:1 ] TRACE 2024/11/13 08:58:26 modbus: send 00 47 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:58:26 modbus: recv 00 47 00 00 00 07 01 03 04 ff ff fa 32
[site ] DEBUG 2024/11/13 08:58:26 grid power: 1486W
[db:1 ] TRACE 2024/11/13 08:58:26 modbus: send 00 48 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:58:26 modbus: recv 00 48 00 00 00 07 01 03 04 ff ff fd fe
[my_pv ] TRACE 2024/11/13 08:58:26 modbus: send 00 49 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:58:27 modbus: recv 00 49 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:58:27 modbus: send 00 4a 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:58:28 modbus: recv 00 4a 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:58:28 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:58:28 modbus: send 00 4b 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:58:28 modbus: recv 00 4b 00 00 00 07 01 03 04 ff ff ff 6b
[db:1 ] TRACE 2024/11/13 08:58:28 modbus: send 00 4c 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:58:28 modbus: recv 00 4c 00 00 00 07 01 03 04 ff ff ff 9e
[site ] DEBUG 2024/11/13 08:58:28 grid currents: [5.14 1.49 0.98]A
[db:1 ] TRACE 2024/11/13 08:58:28 modbus: send 00 4d 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:58:29 modbus: recv 00 4d 00 00 00 07 01 03 04 00 02 22 ce
[site ] DEBUG 2024/11/13 08:58:29 site power: 1486W
[lp-1 ] DEBUG 2024/11/13 08:58:29 charge voltages: [240 241 242]V
[lp-1 ] DEBUG 2024/11/13 08:58:29 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:58:29 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:58:29 charger status: B
[site ] DEBUG 2024/11/13 08:58:40 ----
[lp-1 ] DEBUG 2024/11/13 08:58:40 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:58:40 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:58:40 modbus: send 00 4e 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:58:40 modbus: recv 00 4e 00 00 00 07 01 03 04 ff ff fa 3b
[site ] DEBUG 2024/11/13 08:58:40 grid power: 1477W
[db:1 ] TRACE 2024/11/13 08:58:40 modbus: send 00 4f 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:58:41 modbus: close connection and retry, because of EOF
[db:1 ] TRACE 2024/11/13 08:58:57 modbus: send 00 4f 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:58:57 modbus: recv 00 4f 00 00 00 07 01 03 04 ff ff fd ff
[my_pv ] TRACE 2024/11/13 08:58:57 modbus: send 00 50 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:58:58 modbus: recv 00 50 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:58:58 modbus: send 00 51 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:59:03 modbus: recv 00 51 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:59:03 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:59:03 modbus: send 00 52 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:59:04 modbus: recv 00 52 00 00 00 07 01 03 04 ff ff ff 6b
[db:1 ] TRACE 2024/11/13 08:59:04 modbus: send 00 53 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:59:05 modbus: recv 00 53 00 00 00 07 01 03 04 ff ff ff a0
[site ] DEBUG 2024/11/13 08:59:05 grid currents: [5.13 1.49 0.96]A
[db:1 ] TRACE 2024/11/13 08:59:05 modbus: send 00 54 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:59:05 modbus: recv 00 54 00 00 00 07 01 03 04 00 02 22 cf
[site ] DEBUG 2024/11/13 08:59:05 site power: 1477W
[lp-1 ] DEBUG 2024/11/13 08:59:05 charge voltages: [240 241 243]V
[lp-1 ] DEBUG 2024/11/13 08:59:05 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:59:05 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:59:05 charger status: B
[site ] DEBUG 2024/11/13 08:59:10 ----
[lp-1 ] DEBUG 2024/11/13 08:59:10 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:59:10 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:59:10 modbus: send 00 55 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:59:10 modbus: recv 00 55 00 00 00 07 01 03 04 ff ff fa 41
[site ] DEBUG 2024/11/13 08:59:10 grid power: 1471W
[my_pv ] TRACE 2024/11/13 08:59:10 modbus: send 00 56 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:59:10 modbus: recv 00 56 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:59:10 modbus: send 00 57 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:59:11 modbus: recv 00 57 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:59:11 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:59:11 modbus: send 00 58 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:59:12 modbus: recv 00 58 00 00 00 07 01 03 04 ff ff fe 02
[db:1 ] TRACE 2024/11/13 08:59:12 modbus: send 00 59 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:59:12 modbus: recv 00 59 00 00 00 07 01 03 04 ff ff ff 6c
[db:1 ] TRACE 2024/11/13 08:59:12 modbus: send 00 5a 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:59:12 modbus: recv 00 5a 00 00 00 07 01 03 04 ff ff ff a0
[site ] DEBUG 2024/11/13 08:59:12 grid currents: [5.1 1.48 0.96]A
[db:1 ] TRACE 2024/11/13 08:59:12 modbus: send 00 5b 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:59:13 modbus: recv 00 5b 00 00 00 07 01 03 04 00 02 22 d0
[site ] DEBUG 2024/11/13 08:59:13 site power: 1471W
[lp-1 ] DEBUG 2024/11/13 08:59:13 charge voltages: [240 241 243]V
[lp-1 ] DEBUG 2024/11/13 08:59:13 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:59:13 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:59:13 charger status: B
[site ] DEBUG 2024/11/13 08:59:40 ----
[lp-1 ] DEBUG 2024/11/13 08:59:40 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:59:40 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:59:40 modbus: send 00 5c 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:59:40 modbus: close connection and retry, because of EOF
[db:1 ] TRACE 2024/11/13 08:59:56 modbus: send 00 5c 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:59:57 modbus: recv 00 5c 00 00 00 07 01 03 04 ff ff fa 4e
[site ] DEBUG 2024/11/13 08:59:57 grid power: 1458W
[my_pv ] TRACE 2024/11/13 08:59:57 modbus: send 00 5d 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:59:57 modbus: recv 00 5d 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:59:57 modbus: send 00 5e 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:59:58 modbus: recv 00 5e 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:59:58 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:59:58 modbus: send 00 5f 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:59:58 modbus: recv 00 5f 00 00 00 07 01 03 04 ff ff fe 04
[db:1 ] TRACE 2024/11/13 08:59:58 modbus: send 00 60 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:59:59 modbus: recv 00 60 00 00 00 07 01 03 04 ff ff ff 6a
[db:1 ] TRACE 2024/11/13 08:59:59 modbus: send 00 61 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:59:59 modbus: recv 00 61 00 00 00 07 01 03 04 ff ff ff a1
[site ] DEBUG 2024/11/13 08:59:59 grid currents: [5.08 1.5 0.95]A
[db:1 ] TRACE 2024/11/13 08:59:59 modbus: send 00 62 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 09:00:00 modbus: recv 00 62 00 00 00 07 01 03 04 00 02 22 d2
[site ] DEBUG 2024/11/13 09:00:00 site power: 1458W
[lp-1 ] DEBUG 2024/11/13 09:00:00 charge voltages: [240 241 243]V
[lp-1 ] DEBUG 2024/11/13 09:00:00 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 09:00:00 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 09:00:00 charger status: B
[lp-1 ] DEBUG 2024/11/13 09:00:00 wake-up vehicle, attempts left: 2
[site ] DEBUG 2024/11/13 09:00:10 ----
[lp-1 ] DEBUG 2024/11/13 09:00:10 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 09:00:10 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 09:00:10 modbus: send 00 63 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 09:00:11 modbus: recv 00 63 00 00 00 07 01 03 04 ff ff fa 3c
[site ] DEBUG 2024/11/13 09:00:11 grid power: 1476W
[db:1 ] TRACE 2024/11/13 09:00:11 modbus: send 00 64 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 09:00:13 modbus: recv 00 64 00 00 00 07 01 03 04 ff ff fe 06
[my_pv ] TRACE 2024/11/13 09:00:13 modbus: send 00 65 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 09:00:13 modbus: recv 00 65 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 09:00:13 modbus: send 00 66 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 09:00:14 modbus: recv 00 66 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 09:00:14 pv power: 0W
[db:1 ] TRACE 2024/11/13 09:00:14 modbus: send 00 67 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 09:00:14 modbus: recv 00 67 00 00 00 07 01 03 04 ff ff ff 6b
[db:1 ] TRACE 2024/11/13 09:00:14 modbus: send 00 68 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 09:00:15 modbus: recv 00 68 00 00 00 07 01 03 04 ff ff ff 9d
[site ] DEBUG 2024/11/13 09:00:15 grid currents: [5.06 1.49 0.99]A
[db:1 ] TRACE 2024/11/13 09:00:15 modbus: send 00 69 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 09:00:16 modbus: recv 00 69 00 00 00 07 01 03 04 00 02 22 d2
[site ] DEBUG 2024/11/13 09:00:16 site power: 1476W
[lp-1 ] DEBUG 2024/11/13 09:00:16 charge voltages: [240 241 242]V
[lp-1 ] DEBUG 2024/11/13 09:00:16 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 09:00:16 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 09:00:16 charger status: B

Here is my evcc.yaml.

  network:
  port: 7070
  interval: 30s 
  # trial token, valid until 2024-11-14
  sponsortoken:      eyJhbGciOiJIUzI1NiIsInR5cCI6IkpXVCJ9.eyJpc3MiOiJldmNjLmlvIiwic3ViIjoidHJpYWwiLCJleHAiOjE3MzE1ODU2MDAsImlhdCI6MTczMDcyMTYwMCwic3BlIjp0cnVlLCJzcmMiOiJtYSJ9.HtPxfr4_ZJGRfcYOgQkLlRNqTb5YoVtANmgsQi66Y3Y

  log: info
  levels:
  site: debug
  lp-1: debug
  lp-2: debug
  cache: error
  db: error

  modbusproxy:

  meters:
    - name: my_pv
      type: template
      template: huawei-sun2000
      usage: pv

      # Modbus TCP
      modbus: tcpip
      id: 1
      host: 192.168.x.x # #huawei IP
      port: 502 # Port
      timeout: 15s # optional

  chargers:
    - name: my_charger
      type: template
      template: vestel

      # Modbus TCP
      modbus: tcpip
      id: 255
      host: 192.168.x.x # Webasto IP
      port: 502 # Port

  vehicles:
    - name: my_car
      type: template
      template: bmw
      title: IX
      user: Username
      password: Password
      capacity: 70 # Akkukapazität in kWh (optional)

  site:
    title: Home # display name for UI
    meters:
      pv:
        - my_pv # list of pv inverters/ meters

  loadpoints:
    - title: Carport # display name for UI
      charger: my_charger # charger
      mode: "off" 
      priority: 0 
      soc:

  poll:

    mode: charging

    interval: 60m
  estimate: true # set false to disable interpolating between api updates (not recommended)
enable: # pv mode enable behavior
  delay: 1m # threshold must be exceeded for this long
  threshold: 0 
disable: # pv mode disable behavior
  delay: 3m # threshold must be exceeded for this long
  threshold: 0 # maximum import power (W)

  tariffs:
    currency: EUR # three letter ISO-4217 currency code (default EUR)
    grid:
      type: fixed
      price: 0.286 # EUR/kWh

    feedin:
      type: fixed
      price: 0.08 # EUR/kWh

    co2:

  mqtt:

  influx:

  eebus:

  messaging:
    events:
      start: # charge start event
        title: Charge started
        msg: Started charging in "${mode}" mode
      stop: # charge stop event
        title: Charge finished
        msg: Finished charging ${chargedEnergy:%.1fk}kWh in ${chargeDuration}.
      connect: # vehicle connect event
        title: Car connected
        msg: "Car connected at ${pvPower:%.1fk}kW PV"
      disconnect: # vehicle connected event
        title: Car disconnected
        msg: Car disconnected after ${connectedDuration}
      soc: # vehicle soc update event
        title: Soc updated
        msg: Battery charged to ${vehicleSoc:%.0f}%
      guest: # vehicle could not be identified
        title: Unknown vehicle
        msg: Unknown vehicle, guest connected?
    services:

Thanks in advanced,

Andreas