You signed in with another tab or window. Reload to refresh your session.You signed out in another tab or window. Reload to refresh your session.You switched accounts on another tab or window. Reload to refresh your session.Dismiss alert
I have a Huawei inverter and a BMW IX as a vehicle and a Webasto Unite Wallbox.
So far so well everything was configured, but unfortunately loading doesn't start.
Hello dear community.
I have a Huawei inverter and a BMW IX as a vehicle and a Webasto Unite Wallbox.
So far so well everything was configured, but unfortunately loading doesn't start.
Here is the Log. Does anyone have any advice?
[main ] INFO 2024/11/13 08:53:38 evcc 0.131.5
[main ] INFO 2024/11/13 08:53:38 using config file: /config/evcc.yaml
[db ] INFO 2024/11/13 08:53:38 using sqlite database: /data/evcc.db
[main ] INFO 2024/11/13 08:53:39 listening at :7070
[lp-1 ] DEBUG 2024/11/13 08:53:40 charge total import: 110.000kWh
[site ] INFO 2024/11/13 08:53:40 site config:
[site ] INFO 2024/11/13 08:53:40 meters: grid ✓ pv ✓ battery ✗
[site ] INFO 2024/11/13 08:53:40 grid: power ✓ energy ✓ currents ✓
[site ] INFO 2024/11/13 08:53:40 pv 1: power ✓ energy ✓ currents ✗
[site ] INFO 2024/11/13 08:53:40 vehicles:
[site ] INFO 2024/11/13 08:53:40 vehicle 1: range ✓ finish ✗ status ✓ climate ✗ wakeup ✓
[lp-1 ] INFO 2024/11/13 08:53:40 loadpoint 1:
[lp-1 ] INFO 2024/11/13 08:53:40 mode: off
[lp-1 ] INFO 2024/11/13 08:53:40 charger: power ✓ energy ✓ currents ✓ phases ✗ wakeup ✗
[lp-1 ] INFO 2024/11/13 08:53:40 meters: charge ✓
[lp-1 ] INFO 2024/11/13 08:53:40 charge: power ✓ energy ✓ currents ✓
[lp-1 ] DEBUG 2024/11/13 08:53:40 phase timer inactive
[lp-1 ] DEBUG 2024/11/13 08:53:40 pv timer inactive
[site ] DEBUG 2024/11/13 08:53:40 ----
[lp-1 ] DEBUG 2024/11/13 08:53:40 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:53:40 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:53:41 modbus: send 00 01 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:53:43 modbus: recv 00 01 00 00 00 07 01 03 04 ff ff fa 30
[site ] DEBUG 2024/11/13 08:53:43 grid power: 1488W
[db:1 ] TRACE 2024/11/13 08:53:43 modbus: send 00 02 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:53:44 modbus: recv 00 02 00 00 00 07 01 03 04 ff ff fe 0e
[my_pv ] TRACE 2024/11/13 08:53:44 modbus: send 00 03 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:53:44 modbus: recv 00 03 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:53:44 modbus: send 00 04 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:53:45 modbus: recv 00 04 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:53:45 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:53:45 modbus: send 00 05 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:53:46 modbus: recv 00 05 00 00 00 07 01 03 04 ff ff ff 6a
[db:1 ] TRACE 2024/11/13 08:53:46 modbus: send 00 06 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:53:47 modbus: recv 00 06 00 00 00 07 01 03 04 ff ff ff 93
[site ] DEBUG 2024/11/13 08:53:47 grid currents: [4.98 1.5 1.09]A
[db:1 ] TRACE 2024/11/13 08:53:47 modbus: send 00 07 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:53:47 modbus: recv 00 07 00 00 00 07 01 03 04 00 02 22 c2
[site ] DEBUG 2024/11/13 08:53:47 site power: 1488W
[lp-1 ] DEBUG 2024/11/13 08:53:47 charge voltages: [237 239 239]V
[lp-1 ] DEBUG 2024/11/13 08:53:47 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:53:47 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:53:47 charger status: B
[lp-1 ] INFO 2024/11/13 08:53:47 car connected
[lp-1 ] DEBUG 2024/11/13 08:53:47 vehicle api refresh
[lp-1 ] DEBUG 2024/11/13 08:53:47 pv timer elapse
[lp-1 ] DEBUG 2024/11/13 08:53:47 pv timer inactive
[lp-1 ] DEBUG 2024/11/13 08:53:47 charge total import: 110.000kWh
[main ] DEBUG 2024/11/13 08:53:48 vehicle status: B (IX)
[lp-1 ] INFO 2024/11/13 08:53:48 vehicle updated: unknown -> IX
[lp-1 ] DEBUG 2024/11/13 08:53:48 vehicle status: B
[lp-1 ] DEBUG 2024/11/13 08:53:48 vehicle soc: 32%
[lp-1 ] DEBUG 2024/11/13 08:53:48 vehicle soc limit: 100%
[lp-1 ] DEBUG 2024/11/13 08:53:48 vehicle range: 99km
[site ] DEBUG 2024/11/13 08:54:10 ----
[lp-1 ] DEBUG 2024/11/13 08:54:10 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:54:10 charge currents: [0 0 0]A
[my_pv ] TRACE 2024/11/13 08:54:10 modbus: send 00 08 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:54:10 modbus: close connection and retry, because of EOF
[my_pv ] TRACE 2024/11/13 08:54:26 modbus: send 00 08 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:54:27 modbus: recv 00 08 00 00 00 07 01 03 04 00 00 00 00
[db:1 ] TRACE 2024/11/13 08:54:27 modbus: send 00 09 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:54:27 modbus: recv 00 09 00 00 00 07 01 03 04 ff ff fa 37
[site ] DEBUG 2024/11/13 08:54:27 grid power: 1481W
[my_pv ] TRACE 2024/11/13 08:54:27 modbus: send 00 0a 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:54:27 modbus: recv 00 0a 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:54:27 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:54:27 modbus: send 00 0b 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:54:29 modbus: recv 00 0b 00 00 00 07 01 03 04 ff ff fe 12
[db:1 ] TRACE 2024/11/13 08:54:29 modbus: send 00 0c 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:54:29 modbus: recv 00 0c 00 00 00 07 01 03 04 ff ff ff 6a
[db:1 ] TRACE 2024/11/13 08:54:29 modbus: send 00 0d 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:54:29 modbus: recv 00 0d 00 00 00 07 01 03 04 ff ff ff 91
[site ] DEBUG 2024/11/13 08:54:29 grid currents: [4.94 1.5 1.11]A
[db:1 ] TRACE 2024/11/13 08:54:29 modbus: send 00 0e 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:54:30 modbus: recv 00 0e 00 00 00 07 01 03 04 00 02 22 c4
[site ] DEBUG 2024/11/13 08:54:30 site power: 1481W
[lp-1 ] DEBUG 2024/11/13 08:54:30 vehicle odometer: 41614km
[lp-1 ] DEBUG 2024/11/13 08:54:30 charge voltages: [237 239 240]V
[lp-1 ] DEBUG 2024/11/13 08:54:30 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:54:30 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:54:30 charger status: B
[site ] DEBUG 2024/11/13 08:54:40 ----
[lp-1 ] DEBUG 2024/11/13 08:54:40 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:54:40 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:54:40 modbus: send 00 0f 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:54:40 modbus: close connection and retry, because of EOF
[db:1 ] TRACE 2024/11/13 08:54:56 modbus: send 00 0f 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:54:56 modbus: recv 00 0f 00 00 00 07 01 03 04 ff ff fa 42
[site ] DEBUG 2024/11/13 08:54:56 grid power: 1470W
[db:1 ] TRACE 2024/11/13 08:54:56 modbus: send 00 10 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:54:57 modbus: recv 00 10 00 00 00 07 01 03 04 ff ff fe 14
[my_pv ] TRACE 2024/11/13 08:54:57 modbus: send 00 11 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:54:58 modbus: recv 00 11 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:54:58 modbus: send 00 12 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:54:58 modbus: recv 00 12 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:54:58 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:54:58 modbus: send 00 13 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:54:59 modbus: recv 00 13 00 00 00 07 01 03 04 ff ff ff 6a
[db:1 ] TRACE 2024/11/13 08:54:59 modbus: send 00 14 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:55:00 modbus: recv 00 14 00 00 00 07 01 03 04 ff ff ff 93
[site ] DEBUG 2024/11/13 08:55:00 grid currents: [4.92 1.5 1.09]A
[db:1 ] TRACE 2024/11/13 08:55:00 modbus: send 00 15 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:55:00 modbus: recv 00 15 00 00 00 07 01 03 04 00 02 22 c5
[site ] DEBUG 2024/11/13 08:55:00 site power: 1470W
[lp-1 ] DEBUG 2024/11/13 08:55:00 charge voltages: [238 239 240]V
[lp-1 ] DEBUG 2024/11/13 08:55:00 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:55:00 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:55:00 charger status: B
[site ] DEBUG 2024/11/13 08:55:10 ----
[lp-1 ] DEBUG 2024/11/13 08:55:10 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:55:10 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:55:10 modbus: send 00 16 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:55:11 modbus: recv 00 16 00 00 00 07 01 03 04 ff ff fa 37
[site ] DEBUG 2024/11/13 08:55:11 grid power: 1481W
[my_pv ] TRACE 2024/11/13 08:55:11 modbus: send 00 17 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:55:11 modbus: recv 00 17 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:55:11 modbus: send 00 18 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:55:11 modbus: recv 00 18 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:55:11 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:55:11 modbus: send 00 19 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:55:12 modbus: recv 00 19 00 00 00 07 01 03 04 ff ff fe 13
[db:1 ] TRACE 2024/11/13 08:55:12 modbus: send 00 1a 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:55:13 modbus: recv 00 1a 00 00 00 07 01 03 04 ff ff ff 6a
[db:1 ] TRACE 2024/11/13 08:55:13 modbus: send 00 1b 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:55:14 modbus: recv 00 1b 00 00 00 07 01 03 04 ff ff ff 91
[site ] DEBUG 2024/11/13 08:55:14 grid currents: [4.93 1.5 1.11]A
[db:1 ] TRACE 2024/11/13 08:55:14 modbus: send 00 1c 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:55:14 modbus: close connection and retry, because of EOF
[db:1 ] TRACE 2024/11/13 08:55:30 modbus: send 00 1c 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:55:31 modbus: recv 00 1c 00 00 00 07 01 03 04 00 02 22 c8
[site ] DEBUG 2024/11/13 08:55:31 site power: 1481W
[lp-1 ] DEBUG 2024/11/13 08:55:31 charge voltages: [239 240 241]V
[lp-1 ] DEBUG 2024/11/13 08:55:31 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:55:31 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:55:31 charger status: B
[site ] DEBUG 2024/11/13 08:55:40 ----
[lp-1 ] DEBUG 2024/11/13 08:55:40 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:55:40 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:55:40 modbus: send 00 1d 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:55:41 modbus: recv 00 1d 00 00 00 07 01 03 04 ff ff fa 3a
[site ] DEBUG 2024/11/13 08:55:41 grid power: 1478W
[db:1 ] TRACE 2024/11/13 08:55:41 modbus: send 00 1e 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:55:41 modbus: recv 00 1e 00 00 00 07 01 03 04 ff ff fe 12
[my_pv ] TRACE 2024/11/13 08:55:41 modbus: send 00 1f 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:55:41 modbus: recv 00 1f 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:55:41 modbus: send 00 20 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:55:42 modbus: recv 00 20 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:55:42 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:55:42 modbus: send 00 21 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:55:43 modbus: recv 00 21 00 00 00 07 01 03 04 ff ff ff 69
[db:1 ] TRACE 2024/11/13 08:55:43 modbus: send 00 22 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:55:43 modbus: recv 00 22 00 00 00 07 01 03 04 ff ff ff 94
[site ] DEBUG 2024/11/13 08:55:43 grid currents: [4.94 1.51 1.08]A
[db:1 ] TRACE 2024/11/13 08:55:43 modbus: send 00 23 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:55:44 modbus: recv 00 23 00 00 00 07 01 03 04 00 02 22 c8
[site ] DEBUG 2024/11/13 08:55:44 site power: 1478W
[lp-1 ] DEBUG 2024/11/13 08:55:44 charge voltages: [239 241 241]V
[lp-1 ] DEBUG 2024/11/13 08:55:44 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:55:44 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:55:44 charger status: B
[site ] DEBUG 2024/11/13 08:56:10 ----
[lp-1 ] DEBUG 2024/11/13 08:56:10 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:56:10 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:56:10 modbus: send 00 24 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:56:10 modbus: close connection and retry, because of EOF
[db:1 ] TRACE 2024/11/13 08:56:26 modbus: send 00 24 00 00 00 06 01 03 90 f9 00 02
[lp-1 ] DEBUG 2024/11/13 08:56:26 set charge mode: now
[lp-1 ] DEBUG 2024/11/13 08:56:26 pv timer reset
[lp-1 ] DEBUG 2024/11/13 08:56:26 pv timer inactive
[db:1 ] TRACE 2024/11/13 08:56:26 modbus: recv 00 24 00 00 00 07 01 03 04 ff ff fa 33
[site ] DEBUG 2024/11/13 08:56:26 grid power: 1485W
[db:1 ] TRACE 2024/11/13 08:56:26 modbus: send 00 25 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:56:27 modbus: recv 00 25 00 00 00 07 01 03 04 ff ff fe 0c
[my_pv ] TRACE 2024/11/13 08:56:27 modbus: send 00 26 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:56:27 modbus: recv 00 26 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:56:27 modbus: send 00 27 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:56:28 modbus: recv 00 27 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:56:28 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:56:28 modbus: send 00 28 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:56:29 modbus: recv 00 28 00 00 00 07 01 03 04 ff ff ff 6a
[db:1 ] TRACE 2024/11/13 08:56:29 modbus: send 00 29 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:56:29 modbus: recv 00 29 00 00 00 07 01 03 04 ff ff ff 95
[site ] DEBUG 2024/11/13 08:56:29 grid currents: [5 1.5 1.07]A
[db:1 ] TRACE 2024/11/13 08:56:29 modbus: send 00 2a 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:56:29 modbus: recv 00 2a 00 00 00 07 01 03 04 00 02 22 ca
[site ] DEBUG 2024/11/13 08:56:29 site power: 1485W
[lp-1 ] DEBUG 2024/11/13 08:56:29 charge voltages: [239 240 241]V
[lp-1 ] DEBUG 2024/11/13 08:56:29 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:56:29 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:56:29 charger status: B
[lp-1 ] DEBUG 2024/11/13 08:56:29 max charge current: 13A
[lp-1 ] DEBUG 2024/11/13 08:56:29 charger enable
[lp-1 ] DEBUG 2024/11/13 08:56:29 wake-up timer: start
[site ] DEBUG 2024/11/13 08:56:29 ----
[lp-1 ] DEBUG 2024/11/13 08:56:29 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:56:29 charge currents: [0 0 0]A
[my_pv ] TRACE 2024/11/13 08:56:29 modbus: send 00 2b 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:56:30 modbus: recv 00 2b 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:56:30 modbus: send 00 2c 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:56:31 modbus: recv 00 2c 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:56:31 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:56:31 modbus: send 00 2d 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:56:31 modbus: recv 00 2d 00 00 00 07 01 03 04 ff ff fa 2f
[site ] DEBUG 2024/11/13 08:56:31 grid power: 1489W
[db:1 ] TRACE 2024/11/13 08:56:31 modbus: send 00 2e 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:56:32 modbus: recv 00 2e 00 00 00 07 01 03 04 ff ff fe 0c
[db:1 ] TRACE 2024/11/13 08:56:32 modbus: send 00 2f 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:56:32 modbus: recv 00 2f 00 00 00 07 01 03 04 ff ff ff 68
[db:1 ] TRACE 2024/11/13 08:56:32 modbus: send 00 30 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:56:33 modbus: recv 00 30 00 00 00 07 01 03 04 ff ff ff 94
[site ] DEBUG 2024/11/13 08:56:33 grid currents: [5 1.52 1.08]A
[db:1 ] TRACE 2024/11/13 08:56:33 modbus: send 00 31 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:56:34 modbus: recv 00 31 00 00 00 07 01 03 04 00 02 22 ca
[site ] DEBUG 2024/11/13 08:56:34 site power: 1489W
[lp-1 ] DEBUG 2024/11/13 08:56:34 charge voltages: [239 240 241]V
[lp-1 ] DEBUG 2024/11/13 08:56:34 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:56:34 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:56:34 charger status: B
[site ] DEBUG 2024/11/13 08:56:40 ----
[lp-1 ] DEBUG 2024/11/13 08:56:40 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:56:40 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:56:40 modbus: send 00 32 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:56:41 modbus: recv 00 32 00 00 00 07 01 03 04 ff ff fa 3a
[site ] DEBUG 2024/11/13 08:56:41 grid power: 1478W
[db:1 ] TRACE 2024/11/13 08:56:41 modbus: send 00 33 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:56:41 modbus: recv 00 33 00 00 00 07 01 03 04 ff ff fe 0b
[my_pv ] TRACE 2024/11/13 08:56:41 modbus: send 00 34 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:56:41 modbus: recv 00 34 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:56:41 modbus: send 00 35 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:56:42 modbus: recv 00 35 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:56:42 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:56:42 modbus: send 00 36 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:56:43 modbus: recv 00 36 00 00 00 07 01 03 04 ff ff ff 6a
[db:1 ] TRACE 2024/11/13 08:56:43 modbus: send 00 37 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:56:43 modbus: recv 00 37 00 00 00 07 01 03 04 ff ff ff 97
[site ] DEBUG 2024/11/13 08:56:43 grid currents: [5.01 1.5 1.05]A
[db:1 ] TRACE 2024/11/13 08:56:43 modbus: send 00 38 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:56:44 modbus: recv 00 38 00 00 00 07 01 03 04 00 02 22 ca
[site ] DEBUG 2024/11/13 08:56:44 site power: 1478W
[lp-1 ] DEBUG 2024/11/13 08:56:44 charge voltages: [239 240 241]V
[lp-1 ] DEBUG 2024/11/13 08:56:44 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:56:44 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:56:44 charger status: B
[site ] DEBUG 2024/11/13 08:57:10 ----
[lp-1 ] DEBUG 2024/11/13 08:57:10 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:57:10 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:57:10 modbus: send 00 39 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:57:10 modbus: close connection and retry, because of EOF
[db:1 ] TRACE 2024/11/13 08:57:26 modbus: send 00 39 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:57:27 modbus: recv 00 39 00 00 00 07 01 03 04 ff ff fa 3c
[site ] DEBUG 2024/11/13 08:57:27 grid power: 1476W
[db:1 ] TRACE 2024/11/13 08:57:27 modbus: send 00 3a 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:57:27 modbus: recv 00 3a 00 00 00 07 01 03 04 ff ff fe 03
[my_pv ] TRACE 2024/11/13 08:57:27 modbus: send 00 3b 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:57:28 modbus: recv 00 3b 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:57:28 modbus: send 00 3c 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:57:29 modbus: recv 00 3c 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:57:29 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:57:29 modbus: send 00 3d 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:57:29 modbus: recv 00 3d 00 00 00 07 01 03 04 ff ff ff 6b
[db:1 ] TRACE 2024/11/13 08:57:29 modbus: send 00 3e 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:57:30 modbus: recv 00 3e 00 00 00 07 01 03 04 ff ff ff 9e
[site ] DEBUG 2024/11/13 08:57:30 grid currents: [5.09 1.49 0.98]A
[db:1 ] TRACE 2024/11/13 08:57:30 modbus: send 00 3f 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:57:30 modbus: recv 00 3f 00 00 00 07 01 03 04 00 02 22 cc
[site ] DEBUG 2024/11/13 08:57:30 site power: 1476W
[lp-1 ] DEBUG 2024/11/13 08:57:30 charge voltages: [239 241 241]V
[lp-1 ] DEBUG 2024/11/13 08:57:30 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:57:30 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:57:30 charger status: B
[site ] DEBUG 2024/11/13 08:57:40 ----
[lp-1 ] DEBUG 2024/11/13 08:57:40 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:57:40 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:57:40 modbus: send 00 40 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:57:40 modbus: close connection and retry, because of EOF
[db:1 ] TRACE 2024/11/13 08:57:56 modbus: send 00 40 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:57:58 modbus: recv 00 40 00 00 00 07 01 03 04 ff ff fa 39
[site ] DEBUG 2024/11/13 08:57:58 grid power: 1479W
[my_pv ] TRACE 2024/11/13 08:57:58 modbus: send 00 41 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:57:59 modbus: recv 00 41 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:57:59 modbus: send 00 42 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:58:01 modbus: recv 00 42 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:58:01 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:58:01 modbus: send 00 43 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:58:01 modbus: recv 00 43 00 00 00 07 01 03 04 ff ff fd fd
[db:1 ] TRACE 2024/11/13 08:58:01 modbus: send 00 44 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:58:02 modbus: recv 00 44 00 00 00 07 01 03 04 ff ff ff 6a
[db:1 ] TRACE 2024/11/13 08:58:02 modbus: send 00 45 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:58:02 modbus: recv 00 45 00 00 00 07 01 03 04 ff ff ff a0
[site ] DEBUG 2024/11/13 08:58:02 grid currents: [5.15 1.5 0.96]A
[db:1 ] TRACE 2024/11/13 08:58:02 modbus: send 00 46 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:58:03 modbus: recv 00 46 00 00 00 07 01 03 04 00 02 22 cd
[site ] DEBUG 2024/11/13 08:58:03 site power: 1479W
[lp-1 ] DEBUG 2024/11/13 08:58:03 charge voltages: [239 241 242]V
[lp-1 ] DEBUG 2024/11/13 08:58:03 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:58:03 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:58:03 charger status: B
[lp-1 ] DEBUG 2024/11/13 08:58:03 wake-up vehicle, attempts left: 4
[site ] DEBUG 2024/11/13 08:58:10 ----
[lp-1 ] DEBUG 2024/11/13 08:58:10 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:58:10 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:58:10 modbus: send 00 47 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:58:10 modbus: close connection and retry, because of EOF
[db:1 ] TRACE 2024/11/13 08:58:26 modbus: send 00 47 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:58:26 modbus: recv 00 47 00 00 00 07 01 03 04 ff ff fa 32
[site ] DEBUG 2024/11/13 08:58:26 grid power: 1486W
[db:1 ] TRACE 2024/11/13 08:58:26 modbus: send 00 48 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:58:26 modbus: recv 00 48 00 00 00 07 01 03 04 ff ff fd fe
[my_pv ] TRACE 2024/11/13 08:58:26 modbus: send 00 49 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:58:27 modbus: recv 00 49 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:58:27 modbus: send 00 4a 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:58:28 modbus: recv 00 4a 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:58:28 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:58:28 modbus: send 00 4b 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:58:28 modbus: recv 00 4b 00 00 00 07 01 03 04 ff ff ff 6b
[db:1 ] TRACE 2024/11/13 08:58:28 modbus: send 00 4c 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:58:28 modbus: recv 00 4c 00 00 00 07 01 03 04 ff ff ff 9e
[site ] DEBUG 2024/11/13 08:58:28 grid currents: [5.14 1.49 0.98]A
[db:1 ] TRACE 2024/11/13 08:58:28 modbus: send 00 4d 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:58:29 modbus: recv 00 4d 00 00 00 07 01 03 04 00 02 22 ce
[site ] DEBUG 2024/11/13 08:58:29 site power: 1486W
[lp-1 ] DEBUG 2024/11/13 08:58:29 charge voltages: [240 241 242]V
[lp-1 ] DEBUG 2024/11/13 08:58:29 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:58:29 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:58:29 charger status: B
[site ] DEBUG 2024/11/13 08:58:40 ----
[lp-1 ] DEBUG 2024/11/13 08:58:40 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:58:40 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:58:40 modbus: send 00 4e 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:58:40 modbus: recv 00 4e 00 00 00 07 01 03 04 ff ff fa 3b
[site ] DEBUG 2024/11/13 08:58:40 grid power: 1477W
[db:1 ] TRACE 2024/11/13 08:58:40 modbus: send 00 4f 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:58:41 modbus: close connection and retry, because of EOF
[db:1 ] TRACE 2024/11/13 08:58:57 modbus: send 00 4f 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:58:57 modbus: recv 00 4f 00 00 00 07 01 03 04 ff ff fd ff
[my_pv ] TRACE 2024/11/13 08:58:57 modbus: send 00 50 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:58:58 modbus: recv 00 50 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:58:58 modbus: send 00 51 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:59:03 modbus: recv 00 51 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:59:03 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:59:03 modbus: send 00 52 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:59:04 modbus: recv 00 52 00 00 00 07 01 03 04 ff ff ff 6b
[db:1 ] TRACE 2024/11/13 08:59:04 modbus: send 00 53 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:59:05 modbus: recv 00 53 00 00 00 07 01 03 04 ff ff ff a0
[site ] DEBUG 2024/11/13 08:59:05 grid currents: [5.13 1.49 0.96]A
[db:1 ] TRACE 2024/11/13 08:59:05 modbus: send 00 54 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:59:05 modbus: recv 00 54 00 00 00 07 01 03 04 00 02 22 cf
[site ] DEBUG 2024/11/13 08:59:05 site power: 1477W
[lp-1 ] DEBUG 2024/11/13 08:59:05 charge voltages: [240 241 243]V
[lp-1 ] DEBUG 2024/11/13 08:59:05 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:59:05 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:59:05 charger status: B
[site ] DEBUG 2024/11/13 08:59:10 ----
[lp-1 ] DEBUG 2024/11/13 08:59:10 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:59:10 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:59:10 modbus: send 00 55 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:59:10 modbus: recv 00 55 00 00 00 07 01 03 04 ff ff fa 41
[site ] DEBUG 2024/11/13 08:59:10 grid power: 1471W
[my_pv ] TRACE 2024/11/13 08:59:10 modbus: send 00 56 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:59:10 modbus: recv 00 56 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:59:10 modbus: send 00 57 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:59:11 modbus: recv 00 57 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:59:11 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:59:11 modbus: send 00 58 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:59:12 modbus: recv 00 58 00 00 00 07 01 03 04 ff ff fe 02
[db:1 ] TRACE 2024/11/13 08:59:12 modbus: send 00 59 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:59:12 modbus: recv 00 59 00 00 00 07 01 03 04 ff ff ff 6c
[db:1 ] TRACE 2024/11/13 08:59:12 modbus: send 00 5a 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:59:12 modbus: recv 00 5a 00 00 00 07 01 03 04 ff ff ff a0
[site ] DEBUG 2024/11/13 08:59:12 grid currents: [5.1 1.48 0.96]A
[db:1 ] TRACE 2024/11/13 08:59:12 modbus: send 00 5b 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 08:59:13 modbus: recv 00 5b 00 00 00 07 01 03 04 00 02 22 d0
[site ] DEBUG 2024/11/13 08:59:13 site power: 1471W
[lp-1 ] DEBUG 2024/11/13 08:59:13 charge voltages: [240 241 243]V
[lp-1 ] DEBUG 2024/11/13 08:59:13 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 08:59:13 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 08:59:13 charger status: B
[site ] DEBUG 2024/11/13 08:59:40 ----
[lp-1 ] DEBUG 2024/11/13 08:59:40 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 08:59:40 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 08:59:40 modbus: send 00 5c 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:59:40 modbus: close connection and retry, because of EOF
[db:1 ] TRACE 2024/11/13 08:59:56 modbus: send 00 5c 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 08:59:57 modbus: recv 00 5c 00 00 00 07 01 03 04 ff ff fa 4e
[site ] DEBUG 2024/11/13 08:59:57 grid power: 1458W
[my_pv ] TRACE 2024/11/13 08:59:57 modbus: send 00 5d 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 08:59:57 modbus: recv 00 5d 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 08:59:57 modbus: send 00 5e 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 08:59:58 modbus: recv 00 5e 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 08:59:58 pv power: 0W
[db:1 ] TRACE 2024/11/13 08:59:58 modbus: send 00 5f 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 08:59:58 modbus: recv 00 5f 00 00 00 07 01 03 04 ff ff fe 04
[db:1 ] TRACE 2024/11/13 08:59:58 modbus: send 00 60 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 08:59:59 modbus: recv 00 60 00 00 00 07 01 03 04 ff ff ff 6a
[db:1 ] TRACE 2024/11/13 08:59:59 modbus: send 00 61 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 08:59:59 modbus: recv 00 61 00 00 00 07 01 03 04 ff ff ff a1
[site ] DEBUG 2024/11/13 08:59:59 grid currents: [5.08 1.5 0.95]A
[db:1 ] TRACE 2024/11/13 08:59:59 modbus: send 00 62 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 09:00:00 modbus: recv 00 62 00 00 00 07 01 03 04 00 02 22 d2
[site ] DEBUG 2024/11/13 09:00:00 site power: 1458W
[lp-1 ] DEBUG 2024/11/13 09:00:00 charge voltages: [240 241 243]V
[lp-1 ] DEBUG 2024/11/13 09:00:00 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 09:00:00 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 09:00:00 charger status: B
[lp-1 ] DEBUG 2024/11/13 09:00:00 wake-up vehicle, attempts left: 2
[site ] DEBUG 2024/11/13 09:00:10 ----
[lp-1 ] DEBUG 2024/11/13 09:00:10 charge power: 0W
[lp-1 ] DEBUG 2024/11/13 09:00:10 charge currents: [0 0 0]A
[db:1 ] TRACE 2024/11/13 09:00:10 modbus: send 00 63 00 00 00 06 01 03 90 f9 00 02
[db:1 ] TRACE 2024/11/13 09:00:11 modbus: recv 00 63 00 00 00 07 01 03 04 ff ff fa 3c
[site ] DEBUG 2024/11/13 09:00:11 grid power: 1476W
[db:1 ] TRACE 2024/11/13 09:00:11 modbus: send 00 64 00 00 00 06 01 03 90 f3 00 02
[db:1 ] TRACE 2024/11/13 09:00:13 modbus: recv 00 64 00 00 00 07 01 03 04 ff ff fe 06
[my_pv ] TRACE 2024/11/13 09:00:13 modbus: send 00 65 00 00 00 06 01 03 7d 40 00 02
[my_pv ] TRACE 2024/11/13 09:00:13 modbus: recv 00 65 00 00 00 07 01 03 04 00 00 00 00
[my_pv ] TRACE 2024/11/13 09:00:13 modbus: send 00 66 00 00 00 06 01 03 7d 6a 00 02
[my_pv ] TRACE 2024/11/13 09:00:14 modbus: recv 00 66 00 00 00 07 01 03 04 00 01 b6 01
[site ] DEBUG 2024/11/13 09:00:14 pv power: 0W
[db:1 ] TRACE 2024/11/13 09:00:14 modbus: send 00 67 00 00 00 06 01 03 90 f5 00 02
[db:1 ] TRACE 2024/11/13 09:00:14 modbus: recv 00 67 00 00 00 07 01 03 04 ff ff ff 6b
[db:1 ] TRACE 2024/11/13 09:00:14 modbus: send 00 68 00 00 00 06 01 03 90 f7 00 02
[db:1 ] TRACE 2024/11/13 09:00:15 modbus: recv 00 68 00 00 00 07 01 03 04 ff ff ff 9d
[site ] DEBUG 2024/11/13 09:00:15 grid currents: [5.06 1.49 0.99]A
[db:1 ] TRACE 2024/11/13 09:00:15 modbus: send 00 69 00 00 00 06 01 03 91 01 00 02
[db:1 ] TRACE 2024/11/13 09:00:16 modbus: recv 00 69 00 00 00 07 01 03 04 00 02 22 d2
[site ] DEBUG 2024/11/13 09:00:16 site power: 1476W
[lp-1 ] DEBUG 2024/11/13 09:00:16 charge voltages: [240 241 242]V
[lp-1 ] DEBUG 2024/11/13 09:00:16 detected connected phases: 3p
[lp-1 ] DEBUG 2024/11/13 09:00:16 charge total import: 110.000kWh
[lp-1 ] DEBUG 2024/11/13 09:00:16 charger status: B
Here is my evcc.yaml.
Thanks in advanced,
Andreas
The text was updated successfully, but these errors were encountered: