The SDM120-Modbus single phase electricity meter provides MID certified electricity monitoring up to 45A, ideal for monitoring the electricity supply of heat pumps and EV chargers. A USB to RS485 converter is needed to read from the modbus output of the meter such as: https://www.amazon.co.uk/gp/product/B07SD65BVF. The SDM120 meter comes in a number of different variants, be sure to order the version with a modbus output.
read_interval: Interval between readings in seconds
[[SDM120]]
Type = EmonHubMinimalModbusInterfacer
[[[init_settings]]]
device = /dev/ttyUSB0
baud = 2400
[[[runtimesettings]]]
pubchannels = ToEmonCMS,
read_interval = 10
nodename = sdm120
# prefix = sdm_
[[[[meters]]]]
[[[[[sdm120]]]]]
address = 1
registers = 0,6,12,18,30,70,72,74,76
names = V,I,P,VA,PF,FR,EI,EE,RI
precision = 2,3,1,1,3,3,3,3,3
[[SDM120]]
Type = EmonHubMinimalModbusInterfacer
[[[init_settings]]]
device = /dev/ttyUSB0
baud = 2400
[[[runtimesettings]]]
pubchannels = ToEmonCMS,
read_interval = 10
nodename = sdm120
# prefix = sdm_
[[[[meters]]]]
[[[[[sdm120a]]]]]
address = 1
registers = 0,6,12,18,30,70,72,74,76
names = V,I,P,VA,PF,FR,EI,EE,RI
precision = 2,3,1,1,3,3,3,3,3
[[[[[sdm120b]]]]]
address = 2
registers = 0,6,12,18,30,70,72,74,76
names = V,I,P,VA,PF,FR,EI,EE,RI
precision = 2,3,1,1,3,3,3,3,3