Unable to set Heatit Z-TRM3 thermostat setpoint to 25.5C or lower #2435
Comments
I have a few of the same thermostats and same issue. For completeness, the firmware version of the HeatIt Z-TRM3 is 4.00. Link to a Norwegian forum where the same behavior and issue was observed: https://www.hjemmeautomasjon.no/forums/topic/6330-z-trm3-target-temperature-f%C3%A5r-ikke-satt |
Some scanning of the OZW source for suggesting a fix:
From the linked forum thread it seems HeatIt claims the thermostat reports that it needs 2 bytes for the setpoint. Disclaimer: I have never looked at the OZW source before today, so perhaps I am way off 😃 Edit: I was hoping the OZW logs have "Received capabilities of thermostat setpoint" to debug what is the actual reported min and max (
|
I know it‘s not the smartest way, but I flashed my thermostat with the unofficial firmware. You don‘t need a flashing cable, updating works with a zwave usb-stick. I wrote a litte bit more information in this PR: #2364 |
For those that don't understand Norwegian, I'd like to point out that the firmware is not "unofficial", per se. It is delivered from Thermofloor, but it doesn't pass Z-Wave certification, which is why we shouldn't rely on it. We should instead try to fix open-zwave to work with the setpoint capabilities report that defines how the setpoint should be sent to the device. |
Yes, since this seems to happen with a number of thermostats, it seems OZW
is missing this feature.
I have a PDF and alternative firmware from Thermofloor where they document
their findings on the problem.
In a nutshell it seems that the capabilities report where the min- and
maximum temperature are reported, this information is passed with a field
size for the minimum and maximum temperature. According to them, since the
minimum temperature field has a size of 2 bytes, this is the minimum size
for the setpoint command as well.
So in essence, this size information needs to be cached per thermostat node
and then applied when building the setpoint payload.
I am willing to help out, but since I never worked on OZW I'm still in the
exploration phase and I need to get a development platform as the
HomeAssistant docker is not the right way of altering the source. Unless
someone is already working on caching the minimum and maximum
temperature bounds for the setpoint command, in which case retaining the
field size should be a breeze - but I did not figure out if that is
implemented yet.
…On Sat, Oct 31, 2020 at 9:52 AM Robin Smidsrød ***@***.***> wrote:
For those that don't understand Norwegian, I'd like to point out that the
firmware is not "unofficial", per se. It is delivered from Thermofloor, but
it doesn't pass Z-Wave certification, which is why we shouldn't rely on it.
We should instead try to fix open-zwave to work with the setpoint
capabilities report that defines how the setpoint should be sent to the
device.
—
You are receiving this because you are subscribed to this thread.
Reply to this email directly, view it on GitHub
<#2435 (comment)>,
or unsubscribe
<https://github.com/notifications/unsubscribe-auth/AAOMT6JA5UWHQILMYBW536TSNPF4NANCNFSM4TAQVZMA>
.
|
I'm legitimately curious how this interpretation can be derived from the spec (section 4.114.9 Thermostat Setpoint Capabilities Report Command).
How does it relate to the size in the Set command? It literally says the Min Value Size field is the size of the Min Value field. How would a developer (e.g. OpenZWave) know to interpret it the same way Heat-it says? Why is it the minimum value size field and not the maximum? Are they guaranteed to be the same so it's OK to pick either? There is this ambiguous statement in section 4.114.3 Thermostat Setpoint Set Command:
First of all, Thermostat Setpoint Supported Report Command does not report any precision, scale or size fields. Secondly, the phrase MUST means the thermostat is required to accept the same format it reports, but it doesn't say anything about not supporting other valid formats, and OZW is sending a valid command. I could see that statement, along with the Capabilities Report, being interpreted to mean what Heat-it is saying. However, it doesn't say which field, min or max, is supposed to be used. I guess you hope they are the same? Assuming this is the interpretation being used, and it is in fact required for certification, it would be safer for OZW to use these fields as has been stated. I am not privy to the certification process and what Heat-it has been told, so I am not at all saying they are wrong, just trying to understand where this requirement came from. From an amateur perspective looking strictly at the spec docs, I don't see where. I tried to follow the thread via Google Translate. What was the consensus on support from other hubs? I thought I saw only the Fibaro Home Center was working and no other hubs were, or is it just OpenZWave that doesn't work? I know SmartThings has a 3rd party device handler (RBoy Apps) which seems to be an official handler developed in coordination with the vendor. Does it work with vanilla SmartThings? |
The Norwegian thread and goes all over the place but since OpenHab and HA
both use OZW under the hood, both are affected.
I wonder if some other thermostats with issues around the setpoint command
have the same problem, or that Heatit is the only one (I thought I found a
few others but I went through so many Google results I've lost overview).
In any case I think Heatit is right that, as you also pointed out, that the
capability report is supposed to denote something about the field size, and
the only two sizes in there are the min and max.
It's not specified explicitly that the max temp size has to be equal or
larger than the min temp size but I guess it's safe to assume this is the
case. In case it is desired to handle that, doing a min(sizemin, sizemax)
should cover that.
Reversing the argument, what harm would there be in using the min temp
field size for the setpoint command? Worst case scenario would be that a
zero byte is added to the payload of thermostats that would have accepted a
smaller field size, right? Or are you worried it would break this command
for other thermostats?
Alternatively this new behavior could be placed in the device xml behind an
optional switch to handle the setpoint field width like heatit claims its
supposed to be.
On a side note, their min temp size and max temp size is both 2 bytes in
that report.
…On Sat, 31 Oct 2020, 18:12 Keith Pine, ***@***.***> wrote:
In a nutshell it seems that the capabilities report where the min- and
maximum temperature are reported, this information is passed with a field
size for the minimum and maximum temperature. According to them, since the
minimum temperature field has a size of 2 bytes, this is the minimum size
for the setpoint command as well.
I'm legitimately curious how this interpretation can be derived from the
spec (section 4.114.9 Thermostat Setpoint Capabilities Report Command).
*Min Value Size (3 bits)*
This field is used to indicate the length in bytes of the *Min Value
field*.
This field MUST be set to 1, 2 or 4.
How does it relate to the size in the Set command? It literally says the
Min Value Size field is the size of the Min Value field. How would a
developer (e.g. OpenZWave) know to interpret it the same way Heat-it says?
Why is it the minimum value size field and not the maximum? Are they
guaranteed to be the same so it's OK to pick either?
There is this ambiguous statement in section 4.114.3 Thermostat Setpoint
Set Command:
A supporting node MUST support the same format of Precision, Scale and
Size fields values as it sends in
the Thermostat Setpoint Supported Report Command or Thermostat Setpoint
Capabilities Report
Command.
First of all, Thermostat Setpoint Supported Report Command does not report
any precision, scale or size fields. Secondly, the phrase *MUST* means
the thermostat is required to accept the same format it reports, but it
doesn't say anything about not supporting other valid formats, and OZW is
sending a valid command.
I could see that statement, along with the Capabilities Report, being
interpreted to mean what Heat-it is saying. However, it doesn't say which
field, min or max, is supposed to be used. I guess you hope they are the
same? Assuming this is the interpretation being used, and it is in fact
required for certification, it would be safer for OZW to use these fields
as has been stated.
I am not privy to the certification process and what Heat-it has been
told, so I am not at all saying they are wrong, just trying to understand
where this requirement came from. From an amateur perspective looking
strictly at the spec docs, I don't see where.
I tried to follow the thread via Google Translate. What was the consensus
on support from other hubs? I thought I saw only the Fibaro Home Center was
working and no other hubs were, or is it just OpenZWave that doesn't work?
I know SmartThings has a 3rd party device handler (RBoy Apps) which seems
to be an official handler developed in coordination with the vendor. Does
it work with vanilla SmartThings?
—
You are receiving this because you are subscribed to this thread.
Reply to this email directly, view it on GitHub
<#2435 (comment)>,
or unsubscribe
<https://github.com/notifications/unsubscribe-auth/AAOMT6LS52EAUQFY5JNCP23SNRAQPANCNFSM4TAQVZMA>
.
|
OpenHAB is an independent implementation of Z-Wave in Java, no relation to OZW. The thread also says Homeseer doesn't work, so I guess they've all independently done it wrong. Are the working controllers actually going "by the spec", or do they implement a workaround for Heat-it? That I'm not clear on. SDS14223 lists the interview process for the setpoint class, and has a pretty non-ambiguous table for the Set command. Does "user defined" have a different meaning than I would think of? |
I've sent an email to Heat-it/Thermofloor making them aware of this bug report, asking them to clarify how their thermostats implement the thermostat setpoint specification mentioned above. Hopefully someone there will take the time to actually respond here with some more details, so the problem can be solved once and for all, in a way that is consistent with the ZWave specification. |
They sent me a document containing an alternative firmware, instructions to patch and most importantly a document detailing what they concluded is wrong and how to read the spec according to them. @kpine sorry I thought I inferred from that thread that OpenHAB used OZW as well; which means whenever we figure out what is wrong that still leaves other stacks to be fixed. About that screenshot: I was linked the Z-wave specification before which is the same document Heat-It seemed to use but it differs from yours: the capabilities report apparently defines the format which is needed for the setpoint command, so while there is some freedom at the setpoint format, demanding a specific number of bytes or precision is also possible. In my fork I now implemented this, where the capability report is parsed to retain the number of bytes and precision and applied at the setpoint command. The thermostat is actually reacting to these payloads, but unfortunately its setting the setpoint to wildly different values so something is still wrong. |
My screenshot is from document SDS14223 - Z-Wave Command Class Control Specification. The Control Specification defines how controlling nodes (i.e. openzwave) are supposed to act and the table I listed shows how the Setpoint Set command is supposed to be formatted. According to that, the size argument can be set by the user, but the scale value cannot. The screenshot with the Set and Report payloads is from SDS13781 - Z-Wave Application Command Class Specification. Regarding the test report, I'm not sure what it's supposed to be showing. Is this from Si Labs or Heat-it? I don't have any disagreements with the data it shows. The statement is that OZW is not following the spec (using a size of 1), but the report does not show anything relevant to that. Did I miss something? |
Thermofloor has responded back by email, and they only state that they've talked with several people from Open-ZWave project in the past, so they aren't interested in spending time responding to this again. I tried getting the names of who they spoke to, but they weren't interested in providing this. |
@kpine from SDS14223 v11, 4.19.1 shows the diagram for the interview for a v3 node, where setpoint capabilities report is first issued before issuing the setpoint. In Table 30 is says for the Setpoint Value: If nodes are version 3 or newer: User defined among supported values, If nodes are version 1 or 2: User defined. I am not saying this is the only correct interpretation of the spec (which is fairly ambiguous on how those capabilities are to be used, for example if max uses less bytes than min, or the precision differs between min and max) but I do think its implementable, and I assume its backwards compatible if the older versions just allowed any user defined format. HeatIt mailed me back on my trace and suggested that this command works for them: Below is a trace using my fork I made for 14 degrees for reference: Note how the 3rd byte in this sequence is 0x00 for them and 0x01 for mine - this seems to be the layer below the command layer and I have not yet found the protocol specification to explain to me what that one does. @kpine perhaps you know? |
For the interview, in v1 and v2, the controller must enumerate all of the "ambiguous" setpoint values. In V3 it only needs to enumerate the setpoints that it says are supported. This is because all thermostats do not implement the setpoints the same for V1/2. Yes, OZW can use the same size/scale/precision during the Get phase of the interview and use the same values, as the device is required to support those. I have not disputed that. For the table I quoted, it clearly says the size value is user defined; it makes no distinction between v1/2 and 3. The only one that is clarified is for the "Setpoint Value" which means the user can only select from the setpoints that are supported in V3, otherwise it's completely user defined. Notice in that same section there is a specific mention of the scale argument:
Why doesn't it say that for the size value if it's also true? Of course there is nothing about the min/max values. No one is required to listen to me, certainly not Heat-it. As I said, I'm just trying to learn and so far I'm not convinced that OZW is doing anything wrong. Hopefully sometime soon Fishwaldo will eventually correct me or not. 😃
That's a multichannel encapsulated command (SDS13783). 60 - COMMAND_CLASS_MULTI_CHANNEL There are a couple reasons why the value could be 0. I don't know why it needs to be 0 in this scenario (SDS13783 describes it). If you use the PC-Controller software, there is an option to encapsulate the command and you can tweak the source and destination endpoints to experiment if you want. |
FYI, my older tstat with V2 Setpoint and multi-channel association has no problem accepting an encapsulated command that comes from source endpoint 1. Not sure if there's a requirement one way or the other.
0x60, 0x0d, 0x01, 0x01, 0x43, 0x01, 0x01, 0x09, 0x47
|
I discovered the issue, and it was my own fault. I messed with the size and
precision but I did not patch the function which computes the size of the
value.
After fixing this, I can now control the z-trm3 from openzwave as intended.
I will put this behavior behind a compat flag to limit the impact to only
thermostats which need it.
…On Sun, 8 Nov 2020, 18:32 Keith Pine, ***@***.***> wrote:
FYI, my older tstat with V2 Setpoint and multi-channel association has no
problem accepting an encapsulated command that comes from source endpoint
1. Not sure if there's a requirement one way or the other.
2020-11-08 09:24:56.230627583 [20201108 9:24:56.230 PST] [ozw.library] [info]: Info - Node: 5 Sending (Send) message (Callback ID=0xb8, Expected Reply=0x13) - MultiChannel Encapsulated (instance=1): ThermostatSetpointCmd_Set (Node=5): 0x01, 0x10, 0x00, 0x13, 0x05, 0x09, 0x60, 0x0d, 0x01, 0x01, 0x43, 0x01, 0x01, 0x09, 0x47, 0x25, 0xb8, 0x0d
*0x60, 0x0d, 0x01, 0x01, 0x43, 0x01, 0x01, 0x09, 0x47*
2020-11-08 09:24:57.874438255 [20201108 9:24:57.874 PST] [ozw.library] [debug]: Detail - Node: 5 Received: 0x01, 0x11, 0x00, 0x04, 0x00, 0x05, 0x09, 0x60, 0x0d, 0x01, 0x01, 0x43, 0x03, 0x01, 0x09, 0x47, 0xca, 0x00, 0x4e
2020-11-08 09:24:57.874549177 [20201108 9:24:57.874 PST] [ozw.library] [info]: Info - Node: 5 Response RTT 368 Average Response RTT 399
2020-11-08 09:24:57.874587271 [20201108 9:24:57.874 PST] [ozw.library] [info]: Info - Node: 5 Received a MultiChannelEncap from node 5, endpoint 1 for Command Class COMMAND_CLASS_THERMOSTAT_SETPOINT
2020-11-08 09:24:57.874666065 [20201108 9:24:57.874 PST] [ozw.library] [debug]: Detail - Node: 5 Value Updated: old value=70, new value=71, type=decimal
—
You are receiving this because you are subscribed to this thread.
Reply to this email directly, view it on GitHub
<#2435 (comment)>,
or unsubscribe
<https://github.com/notifications/unsubscribe-auth/AAOMT6KZPVWLWEQA3ISQQTTSO3IZVANCNFSM4TAQVZMA>
.
|
@Cyberwizzard What's left to get this pushed to the container on Docker Hub and close this issue? |
@robinsmidsrod It is essentially done and I have it up and running in my house; the only problem is that on the OZW code I need an instance number in a function which does not have it right now, so I hard-coded it. For anyone with a Z-TRM3 this will not matter, but it needs to be fixed before I can make a pull-request. @kpine or @Fishwaldo - at https://github.com/Cyberwizzard/open-zwave/blob/master/cpp/src/command_classes/ThermostatSetpoint.cpp#L284 I hard-code the instance index to 1 as SetValue on that class does not get an instance ID. How would I get this in a neat manner? |
After quite a lot of troubleshooting with my Thermofloor Heatit TF 058 (aka. Z-TRM3) thermostat I think I've found a bug, and I'm unsure how to approach the issue.
As mentioned in the headline, I'm unable to set the thermostat (heating) setpoint to a value below 26C. By looking carefully at the ThermostatSetpointCmd_Set lines, I was able to understand that it seems to be related to encoding of integers below 256.
These three commands work (i.e. the setpoint is reported back as changed to the new value):
This command fails (i.e. the old setpoint is reported back unchanged):
First of all, is there a compatibility flag available to force the setpoint value to always be sent using 2 bytes, even when the value is below 256? I'm fairly certain that should solve the immediate issue, but not the root cause.
I'm not exactly sure what you need from the log file to debug this further. I was trying out a lot of different configurations in
thermofloor/heatit058.xml
, so my log file is full of trial-and-error issues.Using ozwdaemon docker build 175 together with Home Assistant 0.116.2. Aeotec Z-Stick Gen5 USB controller.